XPander Smoke and Heat Detectors
General
Do not install any XPander equipment until a full site survey has been completed using the
XPander site survey tool. A maximum of 5 interfaces are permitted for each site. For sites
that require more than 5 interfaces please contact Apollo. All installation engineers must
have had certifi ed XPander training.
The XPander smoke and heat detector variants are available under the following part
numbers:
Complete Units
Part Number
XPA-CB-12034-APO
XPA-CB-13032-APO
XPA-CB-11170-APO
XPA-CB-11171-APO
Spares
Part Number
XPA-WB-10022-APO
XPA-OP-12034-APO
XPA-OH-13023-APO
XPA-HT-11170-APO
XPA-HT-11171-APO
The installation must conform to BS5839-1:2013 (or applicable local codes). All detectors are
suitable for indoor use only.
Installation
All detectors must be sited in accordance with the original approved design and site
survey details. Where practical the detector's LED should face towards the room's
entrance.
1.
Twist the ceiling mounting plate anti-clockwise to remove it from the mounting base.
2.
The ceiling mounting plate must be fi tted using both mounting holes and suitable
fi xings or fasteners (see Fig. 1).
Note: Any screw heads must be fl ush or semi fl ush with the internal surface of the ceiling
mount otherwise the battery PCB may be damaged.
3.
Attach the mounting base to the ceiling mounting plate ensuring the tamper switch
spring assembly makes contact. Locate the three lugs and twist clockwise.
4.
Fit the detector to the mounting base.
5.
Fit the power jumper shorting link and commission the unit according to the XPander
commissioning guide PP2286.

Installation Guide

Description
XPander Optical detector with base
XPander Multisensor detector with base
XPander Heat A1R detector with base
XPander Heat CS detector with base
Description
XPander Mounting base only
XPander Optical head only
XPander Multisensor head only
XPander Heat A1R head only
XPander Heat CS head only
1