Alarms
Compressor high pressure
The pressure of the operating compressor is two high, the pressure
protection switch compressor is triggered
Lack of cooling, clogged condenser, high temperature of the
•
cooling water
The unit is overfilled with refrigerant
•
Manual reset (unmount the cap of the pressure
o
protection switch compressor, green reset button)
Compressor low pressure
The pressure of the operating compressor is too low, the pressure
protection switch compressor is triggered
Insufficient refrigerant
•
Clogged filter dehydrator
•
Lack of blowing of the evaporator
•
Automatic reset - pressure protection switch
o
compressor
Compressor high temperature
The temperature of the operating compressor engine is high
Clogged filter
•
Insufficient refrigerant
•
Damaged high temperature module (located in the
•
compressor electrical box)
Damaged refrigerant injection system
•
Damaged TEX valves of the evaporators
•
Automatic reset - after power interruption
Compressor overload
The working current of the operating compressor is high
High pressure
•
Unsuitable power supply
•
Damaged compressor
•
Manual reset - motor protection
o
Cooling water no flow
Lack of water flow through the operating condenser
The water pump is not working
•
Damaged water regulation valve
•
Closed valves
•
OM-RCWC-04D11