Airwell X ARV Manuel d'installation et d'entretien - Page 14

Parcourez en ligne ou téléchargez le pdf Manuel d'installation et d'entretien pour {nom_de_la_catégorie} Airwell X ARV. Airwell X ARV 20 pages. Packaged air conditioners

Airwell X ARV Manuel d'installation et d'entretien

REFRIGERANT LINES

²
Supplied precharged in factory:
MAXIMUM LENGTH 25M.
²
Realized on the site by the installer:
MAXIMUM LENGTH 45M.

REFRIGERANT

linking pipes up to 25m:
²
GAS line:
gas precharge (pipe Ø 1/2")
²
LIqUID line (above to 2m):
55 g/m (pipe Ø 3/8")
For refrigerant lines with a length between 25 and 45m (to be mounted on the site) the diameters, the refrigerant
charge and the installation safety measures must be determined professionally.
GAS line

PIPES TO BE MADE ON SITE

Condenseur at the same level as the
indoor unit
L. max = 45m
L
minimum slope
1cm/m downwards
This operation should be performed expertly by qualified
professionals (refrigeration engineer) (brazing, vacuum,
charge, etc ...).
Unroll the pipes carefully, in the opposite direction to the
spirals, to avoid bending them.

REFRIGERATION PIPE BENDING

The bending radius of the pipes should be equal to or more than 3,5 times de outside
diameter of the pipe.
Do not bend the pipes consecutively more than three times and do not make more than
12 bends over the complete length of the link.
REFRIGERANT LINES
25m< L < 45m
LIqUID line
PIPE Ø 5/8"
Condenseur higher than the
indoor unit
H. max = 20m
(L+H) max = 45m
L
12
Refrigerant :
tube Ø 1/2"
Condenseur lower than the
(L+H) max = 45m
H
"Discharge" line
"Liquid" line
+ 110 g/m
indoor unit
H. max = 9m
L
H