Autonics TK4H Manuel d'instruction - Page 2
Parcourez en ligne ou téléchargez le pdf Manuel d'instruction pour {nom_de_la_catégorie} Autonics TK4H. Autonics TK4H 2 pages. Simultaneous heating&cooling output pid temperature controllers
Également pour Autonics TK4H : Manuel (2 pages), Manuel du produit (6 pages)
Flow Chart for Setting Group
Run mode
Press any key among
2 sec
※2
,
,
once.
※1
※1
PASS
PASS
PASS ※1
When PW
is valid
PARU
※3
PAR1
When PW is valid
Control output RUN/STOP[ R-5 ]
Set the
SV
Set user parameters
1.5 sec
set value
in DAQMaster
Multi SV Number[ SV-N ]
SV will be automatically
saved after 5 sec.
Heater current monitoring[ CT-A ]
Alarm output1 low-limit set value[ AL!L ]
Alarm output1 high-limit set value[ AL!H ]
Alarm output2 low-limit set value[ AL@L ]
Alarm output2 high-limit set value[ AL@H ]
Alarm output3 low-limit set value[ AL#L ]
Alarm output3 high-limit set value[ AL#H ]
SV-0 set value[ SV-0 ]
SV-1 set value[ SV-1 ]
SV-2 set value[ SV-2 ]
※1. PASS parameter will be displayed only when password is set.
It is not displayed when purchasing the unit since default
SV-3 set value[ SV-3 ]
password is set to 0000 .
If password is not valid, the screen will be shifted to password
code required window.
Press any key among
,
,
to return to password
entering window. Press
key to return to RUN mode.
In case you forget password, contact Autonics after checking
password code.
※2. TK4N/S/SP do not have
key.
key replaces
key.
※3. It is displayed when setting user parameter group
in the integrated device management program (DAQMaster).
※Hold the
key over 2 sec in RUN mode to enter into setting mode.
※ Hold the
key for 1.5 sec while in setting mode to move to other
parameter group.
※ Hold the
key over 3 sec while in setting mode to return to RUN mode.
※ Press the
key at the lowest level of parameter to move parameter
group screen and press
,
key to move to other parameter group.
※ If there is no additional key operation within 30 sec after entering into setting
mode, it will be automatically returned to RUN mode and previous set value
will be remained.
※ The not-shaded parameters may not be displayed by other parameters
setting, parameter mask setting.
3 sec
Input Types and Range
Input type
Decimal point
Display
Input range (℃)
1
-200 to 1350
KCaH
K (CA)
0.1
-199.9 to 999.9
KCaL
1
-200 to 800
JIcH
J (IC)
0.1
-199.9 to 800.0
JIcL
1
-200 to 800
ECrH
E (CR)
0.1
-199.9 to 800.0
ECrL
1
-200 to 400
TCcH
T (CC)
0.1
-199.9 to 400.0
TCcL
B (PR)
1
0 to 1800
B PR
Thermocouple
R (PR)
1
0 to 1750
R PR
S (PR)
1
0 to 1750
S PR
N (NN)
1
-200 to 1300
N NN
※1
C (TT)
1
0 to 2300
C TT
G (TT)
※2
1
0 to 2300
G TT
1
-200 to 900
LIcH
L (IC)
0.1
-199.9 to 900.0
LIcL
1
-200 to 400
UCcH
U (CC)
0.1
-199.9 to 400.0
UCcL
Platinel II
1
0 to 1390
PLII
Cu 50Ω
0.1
-199.9 to 200.0
CU 5
Cu 100Ω
0.1
-199.9 to 200.0
CU10
1
-200 to 650
JPtH
JPt 100Ω
0.1
-199.9 to 650.0
JPtL
RTD
DPt 50Ω
0.1
-199.9 to 600.0
DPt5
1
-200 to 650
DPtH
DPt 100Ω
0.1
-199.9 to 650.0
DPtL
Nickel 120Ω
1
-80 to 200
NI12
0-10V
AV1
0-5V
AV2
Voltage
-1999 to 9999
1-5V
AV3
Analog
(Display point will be changed
0-100mV
AMV1
according to decimal point position.)
0-20mA
AMA1
Current
4-20mA
AMA2
※1: C (TT): Same temperature sensor as former W5 (TT)
※2: G (TT): Same temperature sesnor as former W (TT)
※2
※2
H-MV
C-MV
Heating MV
Cooliing MV
Monitoring
Monitoring
PAR2
PAR3
PAR4
Auto-tuning RUN/STOP[ AT ]
Input type[ IN-T ]
Alarm output1operation mode[ AL-1 ]
1.5 sec
1.5 sec
1.5 sec
Heating proportional band[ H-P ]
Sensor temperature unit[ UNIT ]
Alarm output1 option[ AL!T ]
Analog low-limit input value[ L-RG ]
Alarm output1 hysteresis[ A!HY ]
Cooling proportional band[ C-P ]
Heating integral time[ H-I ]
Analog high-limit input value[ H-RG ]
Alarm1 N.O./N.C.[ A!N ]
Scaling decimal point[ DOT ]
Alarm1 ON delay time[ A!ON ]
Cooling integral time[ C-I ]
Heating derivative time[ H-D ]
Low-limit scale value[ L-SC ]
Alarm1 OFF delay time[ A!OF ]
High-limit scale value[ H-SC ]
Alarm output2 operation mode[ AL-2 ]
Cooling derivative time[ C-D ]
Dead_overlap band[ DB ]
Display unit[ dUNT ]
Alarm output2 option[ AL@T ]
Input correction[ IN-B ]
Alarm output2 hysteresis[ A@HY ]
Manual reset[ REST ]
Heating hysteresis[ hHYS ]
Input digital filter[ MAvF ]
Alarm 2 N.O./N.C.[ A@N ]
Heating OFF offset[ hOST ]
SV low-limit[ L-SV ]
Alarm 2 ON delay time[ A@ON ]
Cooling hysteresis[ cHYS ]
SV high-limit[ H-SV ]
Alarm 2 OFF delay time[ A@OF ]
Cooling OFF offset[ cOST ]
Control output operation mode[ O-FT ]
Alarm output3 operation mode[ AL-3 ]
MV low-limit[ L-MV ]
Control type[ C-MD ]
Alarm output3 option[ AL#T ]
Auto-tuning mode[ AtT ]
MV high-limit[ H-MV ]
Alarm output3 hysteresis[ A#HY ]
RAMP-up change rate[ RAMU ]
OUT1 control output selection[ OUT1 ]
Alarm 3 N.O./N.C.[ A#N ]
RAMP-down change rate[ RAMD ]
OUT1 SSR drive output type[ O!SR ]
Alarm 3 ON delay time[ A#ON ]
RAMP time unit[ rUNT ]
OUT1 current output range[ O!MA ]
Alarm 3 OFF delay time[ A#OF ]
OUT2 control output selection[ OUT2 ]
LBA time[ LBaT ]
OUT2 current output range[ O@MA ]
LBA band[ LBaB ]
Heating control time[ H-T ]
Analog trans. output 1 mode[ AoM1 ]
Cooling control time[ C-T ]
Trans. output 1 low-limit value[ FsL1 ]
Trans. output 1 high-limit value[ FsH1 ]
Analog trans. output 2 mode[ AoM2 ]
Trans. output 2 low-limit value[ FsL2 ]
Trans. output 2 high-limit value[ FsH2 ]
Comm. address[ ADRS ]
Comm. speed[ BPS ]
Comm. parity bit[ PRTY ]
Comm. stop bit[ STP ]
Comm. response waiting time[ RSwT ]
Comm. write[ COMW ]
3 sec
3 sec
Initial Display When Power ON
When power is supplied, whole display parts flash for 1 sec. Afterwards, model name and input sensor type
Input range (℉)
will be flash twice and then in enters into RUN mode.
-328 to 2463
-199.9 to 999.9
-328 to 1472
-199.9 to 999.9
-328 to 1472
-199.9 to 999.9
-328 to 752
-199.9 to 752.0
① Whole display part
② Model type display
③ Input type display twice
32 to 3272
Set Value (SV) Setting
32 to 3182
32 to 3182
You can set the temperature to control with
,
,
keys.
-328 to 2372
Set range is within SV low-limit value [ L-SV ] to SV high-limit value [ H-SV ].
32 to 4172
Ex) In case of changing set temperature from 210℃ to 250℃
①
②
32 to 4172
Press any key among
,
,
in RUN mode
-328 to 1652
to enter into SV setting
-199.9 to 999.9
mode.
-328 to 752
Last digit (10
0
digit) on
-199.9 to 752.0
SV display part flashes.
32 to 2534
-199.9 to 392.0
-199.9 to 392.0
-328 to 1202
③
Press
key to raise
④
,
-199.9 to 999.9
or lower the set value.
-199.9 to 999.9
-328 to 1202
-199.9 to 999.9
-112 to 392
Parameter Reset
Press
+
+
to reset all parameters in memory to default value.
Set [ INIT ] parameter to ' YES ' to reset all parameters.
In case password function is on, it is required to enter valid password to reset parameters.
Password is also reset.
Parameter Mask
This function is able to hide unnecessary parameters to user environment or less frequently used parameters in
parameter group. You can set this in the integrated device management program (DAQmaster).
3 sec
Masked parameters are not only displayed. The set value of masked parameters are applied.
For more information, refer to the DAQMaster user manual.
Visit our website (www.autonics.com) to download the DAQmaster program and the user manual.
Before applying mask
PAR2
AT
After applying mask
PAR2
H-P
PAR5
The above is masking auto tuning [ AT ], cooling proportional band [ C-P ], cooling integral time [ C-1 ],
cooling derivative time [ C-D ] parameters in parameter 2 group.
User Parameter Group [ PARU] Setting
Multi SV[ MtSV ]
This function is able to set the frequently used parameters to the user parameter group. You can quickly and
easily set parameter settings. User parameter group can have up to 30 parameters in the integrated device
1.5 sec
management program (DAQMaster).
For more information, refer to the DAQMaster user manual.
Digital input key[ DI-K ]
Visit our website (www.autonics.com) to download the DAQmaster program and the user manual.
DI-1 input terminal function[ DI-1 ]
Run mode
DI-2 input terminal function[ DI-2 ]
Manual control, initial MV[ ItMV ]
PARU
PAR1
PAR2
Manual control, preset MV[ PrMV ]
Sensor error, MV[ ErMV ]
AL!L
AL!H
SV-0
hHYS
The above is setting user parameter group in the DAQMaster with alarm output 1 low-limit value [ AL!L ], alarm output 1
Control stop, MV[ StMV ]
high-limit value [ AL!H ], SV-0 set value [ SV-0 ] parameter of parameter 1 group, heating hysteresis[ hHYS ],
Control stop, alarm output[ StAL ]
cooling hysteresis [ cHYS ] parameters of parameter 2 group, input correction [ IN-B ] parameter of parameter 3
group, alarm output 1 hysteresis [ A!HY ], alarm output 2 hysteresis [ A@HY ] parameters of parameter 4 group.
User level[ USER ]
Auto-tunning
SV setting lock[ LcSV ]
Auto-tuning measures the control subject's thermal characteristics and thermal response rate, and then
Parameter 1group lock[ LcP1 ]
determines the necessary PID time constant. Application of the PID time constant realizes fast response and
Parameter 2group lock[ LcP2 ]
high precision temperature control. (when setting control type [ C-MD ] is set as PID , it is displayed.)
Set [ AT ] parameter to [ ON ] in parameter 2 group to start auto-tuning. To stop auto-tuning, change the set as [ OFF ].
Parameter 3group lock[ LcP3 ]
(It maintains P, I, D values of before auto-tuning.)
Parameter 4group lock[ LcP4 ]
If sensor break error [ OPEN ] occurs during auto-tuning, it stops this operation. If the measured temperature is
over or below the input range, it operates continuously.
Parameter 5group lock[ LcP5 ]
During auto-tuning operation, whole parameters are only available to check.
Password setting[ PWD ]
Alarm
●Alarm operation
Mode
Name
Alarm operation
OFF
-
-
OFF
H
Deviation
DVCC
high-limit
SV
PV
alarm
100℃
110℃
High deviation: Set as 10℃
H
OFF
ON
Deviation
]]DV
low-limit
PV
SV
alarm
90℃
100℃
Low deviation: Set as 10℃
ON
H
Deviation
]DVC
high/low-limit
PV
alarm
90℃
Low deviation : Set as 10℃ , High deviation : Set as 20℃
OFF
H
Deviation
3 sec
3 sec
high/low-limit
CDV]
PV
reserve alarm
90℃
Low deviation : Set as 10℃ , High deviation : Set as 20℃
OFF
H
ON
Absolute
value high-
PVCC
PV
SV
limit alarm
90℃
100℃
Absolute-value: Set as 90℃
OFF
ON
H
Absolute
value low-limit
]]PV
PV
SV
alarm
90℃
100℃
Absolute-value: Set as 90℃
Loop break
-
④ Run mode
LBA
alarm
Sensor break
SBA
-
alarm
Heater break
-
HBA
alarm
※H: Alarm output
hysteresis[ A .HY ]
Press
key to move digit.
(10
0
→ 10¹→
●Alarm option
0
10²→10³→ 10
)
Mode Name
Description
Standard alarm If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF.
AL-A
AL-B
Alarm latch
If it is an alarm condition, alarm output is ON and maintains ON status.
First alarm condition is ignored and from second alarm condition, standard alarm
Standby
AL-C
operates. When power is supplied and it is an alarm condition, this first alarm
sequence 1
condition is ignored and from the second alarm condition, standard alarm operates.
Press
key to save
Alarm latch
If it is an alarm condition, it operates both alarm latch and standby sequence. When
the set value.
and standby
power is supplied and it is an alarm condition, this first alarm condition is ignored and
AL-D
If there is no additional
from the second 1alarm condition, alarm latch operates.
sequence 1
key operations in 3 sec,
the changed SV is
First alarm condition is ignored and from second alarm condition, standard alarm
Standby
automatically saved.
operates. When re-applied standby sequence and if it is alarm condition, alarm output
AL-E
sequence 2
does not turn ON. After clearing alarm condition, standard alarm operates.
Basic operation is same as alarm latch and standby sequence1. It operates not only
Alarm latch
by power ON/OFF, but also alarm set value, or alarm option changing. When re-
AL-F
and standby
applied standby sequence and if it is alarm condition, alarm output does not turn ON.
sequence 2
After clearing alarm condition, alarm latch operates.
※Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON,
changing set temperature, alarm temperature [ AL1 , AL2 ] or alarm operation [ AL-1 , AL-2 ], switching STOP mode
to RUN mode.
Factory Default
●SV setting group [ SV ]
Parameter
SV
●Parameter 1 group [ PAR1 ]
H-P
C-P
H-I
C-I
H-D
C-D
Parameter Factory default Parameter Factory default Parameter Factory default Parameter Factory default
R-S
RUN
SV-N
SV-0
H-I
H-D
CT-A
)0
AL!L
1550
●Parameter 2 group [ PAR2 ]
Parameter Factory default Parameter Factory default Parameter Factory default Parameter Factory default
AT
OFF
H-P
01)0
C-P
01)0
H-I
0000
C-I
0000
●Parameter 3 group [ PAR3 ]
Parameter Factory default Parameter Factory default Parameter Factory default Parameter Factory default
IN-T
KCaH
UNIT
?C
cHYS
IN-B
A!HY
A@HY
L-RG
0)00
H-RG
1)00
DOT
)0
L-SC
00)0
●Parameter 4 group [ PAR4 ]
Parameter Factory default Parameter Factory default Parameter Factory default Parameter Factory default
AL-1
DVCC
AL!T
AL-A
A!HY
001
A!N
NO
A!ON
0000
A!OF
0000
AL-2
]]DV
AL@T
AL-A
A@HY
001
●Parameter 5 group [ PAR5 ]
Description
Parameter Factory default Parameter Factory default Parameter Factory default Parameter Factory default
No alarm output
MtSV
OFF
DI-K
STOP
ON
H
ON
If deviation between PV and SV
DI-1
OFF
as high-limit is higher than set
PV
SV
value of deviation temperature,
DI-2
OFF
90℃
100℃
the alarm output will be ON.
ItMV
AUTO
High deviation: Set as -10℃
※Shaded parameters are for the heating&cooling model.
H
OFF
ON
If deviation between PV and SV
User Manual
as low-limit is higher than set
SV
PV
value of deviation temperature,
100℃
110℃
For the detail information and instructions, please refer to user manual and user manual for communication,
the alarm output will be ON.
Low deviation: Set as -10℃
and be sure to follow cautions written in the technical descriptions (catalog, homepage).
Visit our homepage (www.autonics.com) to download manuals.
If deviation between PV and
OFF
H
ON
SV as high/low-limit is higher
Comprehensive Device Management Program[DAQMaster]
than set value of deviation
SV
PV
100℃
120℃
temperature, the alarm output
DAQMaster is a comprehensive device management software for setting parameters and monitoring
will be ON.
processes. DAQMaster can be downloaded from our website at www.autonics.com.
If deviation between PV and
OFF
ON
H
Item
Minimum specifications
SV as high/low-limit is lower
System
IBM PC compatible computer with Pentium Ⅲ or above
than set value of deviation
SV
PV
Operations
Windows 98/NT/XP/Vista/7/8/10
100℃
120℃
temperature, the alarm output
Memory
256MB+
will be OFF.
Hard disk
1GB+ of available hard disk space
OFF
H
ON
VGA
Resolution: 1024×768 or higher
If PV is higher than the absolute
Others
RS232C serial port (9-pin), USB port
SV
PV
value, the output will be ON.
100℃
110℃
Cautions during Use
Absolute-value: Set as 110℃
1. Follow instructions in 'Cautions during Use'. Otherwise, It may cause unexpected accidents.
ON
H
OFF
2. Check the polarity of the terminals before wiring the temperature sensor.
If PV is lower than the absoulte
For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length.
SV
PV
value, the output will be ON.
For thermocouple (CT) temperature sensor, use the designated compensation wire for extending wire.
100℃
110℃
3. Keep away from high voltage lines or power lines to prevent inductive noise.
Absolute-value: Set as 110℃
In case installing power line and input signal line closely, use line filter or varistor at power line and shielded
It will be ON when it detects
wire at input signal line.
Do not use near the equipment which generates strong magnetic force or high frequency noise.
loop break.
4. Do not apply excessive power when connecting or disconnecting the connectors of the product.
It will be ON when it detects
5. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the
sensor disconnection.
power.
6. Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller.
It will be ON when CT detects
7. When changing the input sensor, turn off the power first before changing.
heater break.
After changing the input sensor, modify the value of the corresponding parameter.
8. 24VAC, 24-48VDC power supply should be insulated and limited voltage/current or Class 2, SELV power
supply device.
9. Do not overlapping communication line and power line.
Use twisted pair wire for communication line and connect ferrite bead at each end of line to reduce the effect
of external noise.
10. Make a required space around the unit for radiation of heat.
For accurate temperature measurement, warm up the unit over 20 min after turning on the power.
11. Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.
12. Do not wire to terminals which are not used.
13. This unit may be used in the following environments.
① Indoors (in the environment condition rated in 'Specifications')
③ Pollution degree 2
Major Products
Photoelectric Sensors
Fiber Optic Sensors
Door Sensors
Door Side Sensors
Area Sensors
Proximity Sensors
Pressure Sensors
Rotary Encoders
Connector/Sockets
Switching Mode Power Supplies
Control Switches/Lamps/Buzzers
I/O Terminal Blocks & Cables
Stepper Motors/Drivers/Motion Controllers
Graphic/Logic Panels
Field Network Devices
Laser Marking System (Fiber, CO₂, Nd: YAG)
Laser Welding/Cutting System
●Password input parameter
Factory default
Parameter
Factory default
0
PASS
0001
AL!H
1550
AL#H
1550
SV-3
0000
AL@L
1550
SV-0
0000
AL@H
1550
SV-1
0000
AL#L
1550
SV-2
0000
H-D
0000
hOST
000
RAMU
000
C-D
0000
cHYS
002
RAMD
000
DB
0000
cOST
000
rUNT
MIN
REST
05)0
L-MV
`0)0
hHYS
002
H-MV
10)0
H-SC
10)0
HEAT
O!SR
STND
O-FT
dUNT
?/O
H-C
O!MA
4-20
IN-B
0000
PID
OUT2
CURR
C-MD
MAvF
00)1
pP
O@MA
4-20
L-SV
-200
AtT
TUN1
H-T
02)0
(Relay)
H-SV
1350
OUT1
CURR
C-T
00@0
(SSR)
A@N
NO
LBaT
0000
BPS
96
A@ON
0000
LBaB
002
PRTY
NONE
A@OF
0000
AoM1
PV
STP
2
AL-3
OFF
FsL1
-200
RSWT
20
AL#T
AL-A
FsH1
1350
COMW
EnA
A#HY
001
AoM2
PV
A#N
NO
FsL2
-200
A#ON
0000
FsH2
1350
A#OF
0000
ADRS
01
1
PrMV
00)0
LcSV
OFF
LcPS
OFF
ErMV
00)0
LcP1
OFF
PWD
0000
StMV
00)0
LcP2
OFF
StAL
CONT
LcP3
OFF
USER
STND
LcP4
OFF
② Altitude max. 2,000m
④ Installation category II
Temperature Controllers
Temperature/Humidity Transducers
SSRs/Power Controllers
Counters
Timers
Panel Meters
Tachometer/Pulse (Rate) Meters
Display Units
Sensor Controllers
http://www.autonics.com
HEADQUARTERS:
18, Bansong-ro 513beon-gil, Haeundae-gu, Busan,
South Korea, 48002
TEL: 82-51-519-3232
E-mail: [email protected]
DRW170598AA