2 LOCATION - GENERAL
2 .11
Location: The APU Mini must be located on a solid wall of sufficient
strength to support the filled weight of the APU Mini, close to the
water source and a suitable overflow position (see Section 10 -
Technical Specification for filled weight) . The APU Mini must not be
installed in a loft space . It must also be considered that the noise
and vibration from the APU Mini may be transmitted through the
structure it is sited on . Ensure the minimum clearance requirements
are followed to allow servicing of the unit .
2 .12
Access and minimum clearance requirements: For emergencies
and maintenance the APU Mini must be easily accessible and have
the minimum clearance around it as laid out in Fig . 2 . Additional
access to the front of the unit will be required to operate the keypad
and view the display .
500
2 .13 Protection: The APU Mini must be located in a dry, frost free area .
2 .14
Ventilation: Ensure an adequate air flow to cool the APU Mini .
Separate the APU Mini from other appliances that generate heat .
Do not block the vent holes on the front cover .
2 .15 Water retention: Site the APU Mini in a location where in the
unlikely event of a water leak, any spillage is contained or routed
to avoid electrics or areas sensitive to water damage . As part of
the AB airgap (CAT 5 fluid isolation) the APU Mini has a weir type
overflow on the front, water will be discharged from this area in the
event of the failure of the inlet valve or non-return valve .
2 .16 Supply inlet pressure: The water supply inlet pressure must not exceed 7 bar .
2 .17 Ambient temperature: The APU Mini must be sited in a location where the
ambient temperature does not drop below 4 °C or exceed 40 °C .
2 .18 Pipework: For optimum performance inlet and outlet pipework must be a
minimum of 15 mm pipe .
150
Fig . 2
- 6 -
2 .19 Static outlet pressure: The static outlet head must be 3 metres below pump
maximum cold fill pressure (vertically above the appliance) .
2 .20 Noise: A flexible hose is supplied as standard which will minimise the
transmission of noise and vibration from the APU Mini pump to the
pipework connected to the appliance outlet . However, care must be taken
when mounting the APU Mini that any noise is not amplified through loose
panels or pipework .
2 .21 Flexible hose: Only use the ADEY hose supplied with the APU Mini .
2 .22 Isolating valves: Separate system isolating valves (non-restrictive) must be
fitted to allow easy service of the APU Mini . Isolating valves must be mounted
where specified to allow the system isolation and removal of the APU Mini if
needed . See Section 4 .14 for installation details .
150
- 7 -