Airflow Uno hab Manuel d'installation et d'utilisation - Page 9
Parcourez en ligne ou téléchargez le pdf Manuel d'installation et d'utilisation pour {nom_de_la_catégorie} Airflow Uno hab. Airflow Uno hab 16 pages. Cavity wall decentralised mechanical ventilation with heat recovery unit
Également pour Airflow Uno hab : Instructions (2 pages), Kit d'installation (16 pages), Manuel d'entretien (2 pages)
m
WARNING
m
CAUTION
© Airflow - we reserve the right to make changes without prior notice
Installation step 3:
m Electrical connection:
If a residual current device is installed in the EC fan supply line, the residual current device must have the following
technical characteristics:
Type A or B with a rated differential current of 30 mA.
The EC fan has a leakage current of <= 3.5 mA, determined according to DIN EN 50178 image 4.
1. Pull the 2-part connector from the fan unit Pos.
2. Pull connector out for connection to the Cable Pos.
3. Wire the connection leads of the control cable (max. outer Ø 6 mm) according to wiring diagram
SD-3/SD-4 (see page 13/14).
Connection control
cable (by customer)
4. Plug together the 2-part connector (fig.9).
5. Insert connector into the unit receptacle (fig.9) and stow the fan connection leads in the EPP casing!
6. Then insert the fan unit up to the stop "outer panel" in the wall installation sleeve (fig.10).
m
CAUTION!
When inserting the fan unit, do not press on the protection guard! (fig.10)
Receptacle
Connector
Connection cable not pictured!
Installation step 4:
1. Insert the inner panel. Do not pinch Cable!
Note mounting direction! The outflow opening must be on top!
Outflow opening Top
Inner panel
Unohab Unit
(fig.8).
ò
(fig.8).
ù
ò
ù
2-Part
connector
fig.9
fig.11
9
Installation and Operating Instructions
Connection fan unit
Complete wall
mounting!
fig.8
fig.10
fig.12