Avantco 178GDICE24FW Manuel d'entretien - Page 8

Parcourez en ligne ou téléchargez le pdf Manuel d'entretien pour {nom_de_la_catégorie} Avantco 178GDICE24FW. Avantco 178GDICE24FW 18 pages. Ice merchandisers

Avantco 178GDICE24FW Manuel d'entretien
Part Testing

Compressor and Capacitor Testing

With the unit 'ON' and controller calling for the
compressor to run, check amperage on 'red' wire coming
from the controller, see table below for values +/- 10%
Model #
178GDICE24FB/W
178GDICE49FB/W
Disconnect wiring from compressor, check resistance
from common to run and start windings. Resistance
should be found (Run to Start = (Runs to Common) + (Start
to Common))
Temperature will change resistance OHM valves
Check windings are not connected to ground by
checking for Ohms from each pin to the shell of the
compressor (Paint must be removed from case when
checking for grounding)
Visually check capacitor for any deformations or leaking
oil like fluids, replace if any is found
Discharge capacitor prior to testing, use a 20,000 ohm, 2
watt carbon resistor, caution resistor will be HOT during
discharge
Capacitor micro-farads = µF +/- 5%, replace if not within
range
www.AvantcoRefrigeration.com
8
Service Manual
Ice Merchandisers
Max Load
Locked Rotor
Amps
Amps (LRA)
7.6 Amps
39.7 Amps
10.6 Amps
55.2 Amps
Fig. 8
Fig. 9
Fig. 10
Fig. 11