A-T Controls TRIAO TMC-4 Manuel d'installation et d'utilisation - Page 14

Parcourez en ligne ou téléchargez le pdf Manuel d'installation et d'utilisation pour {nom_de_la_catégorie} A-T Controls TRIAO TMC-4. A-T Controls TRIAO TMC-4 19 pages.

A-T Controls TRIAO TMC-4 Manuel d'installation et d'utilisation
COMMS CONFIG submenu
Sets type of communication protocol when using one of the communication module options. "Comms" command
C O M M S
type must be selected in the COMMAND CONFIG submenu.
T Y P E :
x x x x
Modbus
Communication
MbusTCP
Type
Profibus
Actuator ID address. Selectable from 1 to 246
U N I T I D :
1
x x
Unit ID
Communication channel data rate.
B A U D R A T E
9600, 19200, 57600, 115200 bps
x x x x
Baud Rate
Communication channel parity setting.
P A R I T Y :
None, Odd, Even
x x x x
Parity
Communication timeout. Determines duration of time which the actuator must receive communication before
T I M E O U T :
entering fault condition.
x x . x x S
10.00 sec
Timeout
SYSTEM CONFIG submenu
Selects type of motor being operated. AC setting is for split-phase AC type motor. DC is for DC motors. This
M O T O R
setting is independent of the AC/DC power supply switch, but should correspond to the switch position.
T Y P E :
x x
AC
Motor Type
Displays count for open and close position since power supplied to controller.
C Y C L E C N T
O P E N :
x x x
C L O S :
x x x
Cycle Count
Clears cycle count. Press [RIGHT] or [CENTER] to select, then press again to confirm and clear counts.
C L E A R C Y C L
C O U N T S
> >
Clear Count
Restores all settings to their default value. Press [RIGHT] or [CENTER] to select, then press again to confirm and
R E S T O R E
reset to default values.
D E F A U L T S
> >
Restore Defaults
Displays current software revision number.
S O F T W A R E
V E R S I O N
x x . x x
Software Version
www.atcontrols.com
Modbus RTU
Modbus/TCP
Profibus DP
14
TMC-4 Control Card
for Electric Actuators
Installation & Maintenance Manual
03/18/21
IOM08139 REVISION 01