Avlite AV-OL-CMI Manuel d'installation et d'entretien - Page 18
Parcourez en ligne ou téléchargez le pdf Manuel d'installation et d'entretien pour {nom_de_la_catégorie} Avlite AV-OL-CMI. Avlite AV-OL-CMI 20 pages. Combined medium intensity obstruction light
36V DC Supply System
Red Status LED Name
Slow
High
Off
Optimal Between 36.0V – 45.0V
1 Quick
Good
2 Quick
Ok
3 Quick
Low
4 Quick
Flat
48V DC Supply System
Red Status LED Name
Slow
High
Off
Optimal Between 48.0V – 60.0V
1 Quick
Good
2 Quick
Ok
3 Quick
Low
4 Quick
Flat
Once the Flat Battery cutoff condition is in effect, the lantern will not turn back on until it sees day light and the battery
voltage is above the 'OK' threshold for at least one minute.
Yellow Status LED
Lantern Status
Off
Standby
Quick Flashing
Day to Night Transitioning
0.15s on, 0.15s off
(Dusk Till Dawn Mode)
2 Quick Flashes
Operational, Not Sychronised
every 2s
1 Quick Flash
Operational, Sychronisation in
every 2s
Progress
Slow Flashing
Operational, Sychronised
1.5s on, 1.5 off
2 Quick Flashes
Operational, Sychronised as
every 11s
Slave
Medium Intensity Obstruction Light
18
AV-OL-MI
Voltage
45.0V and above
Approximately 36.0V
Between 32.4V – 36.0V
Between 28.8V - 32.4V
28.8V and below
Voltage
60.0V and above
Approximately 48.0V
Between 43.2V – 48.0V
Between 38.4V - 43.2V
48.4V and below
Description
Voltage is higher than expected, this may indicate a problem
with the solar regulator.
Voltage is correct for a charged battery
Voltage is correct, this is where the lantern returns to normal
operation
Voltage is a little low, but within expectations.
Voltage is low, this is where the alarm relay is first activated
Voltage is flat, this is where the main LEDs are turned off and
the flat battery cutoff is enabled
Description
Voltage is higher than expected, this may indicate a problem
with the solar regulator.
Voltage is correct for a charged battery
Voltage is correct, this is where the lantern returns to normal
operation
Voltage is a little low, but within expectations.
Voltage is low, this is where the alarm relay is first activated
Voltage is flat, this is where the main LEDs are turned off and
the flat battery cutoff is enabled
Lantern
Description
OFF
Lantern is in Standby Mode
Light is activating and will turn on after detecting 30
OFF
seconds of continuous darkness
ON
Lantern is in Normal operating condition. it is not connect-
ed to any GPS synchronisation
ON
Lantern is 're-syncing' with GPS. THe lantern re-sync's with
GPS every 15 minutes.
ON
Normal operationg condition. Lantern is syncronised to
GPS-enabled lanterns.
ON
Lantern is a Hard Wire Syncronised Slave.