Miller Axcess 675 Manuel du propriétaire - Page 34
Parcourez en ligne ou téléchargez le pdf Manuel du propriétaire pour {nom_de_la_catégorie} Miller Axcess 675. Miller Axcess 675 48 pages. Automatic welding interface and arc welding power source
Également pour Miller Axcess 675 : Manuel du propriétaire (48 pages)
8-4. Network And Module Status LED's
Network Status LED's
A.
The following is a network status LED:
LED4 on the PCM circuit board.
Status
Off
The circuit board is not on-line with the network or there is no power applied to the circuit board.
Green
The circuit board is operating normally and the on-line connection is made with the network.
Flashing Green
The circuit board is waiting for an on-line connection to be made with the network.
Red
The circuit board has encountered a communication link failure with the network. Check DeviceNet cable connections. Verify
dip switch positions according to Sections 1-2 and 1-3. Replace circuit board if necessary.
Module Status LED's
B.
The following is a module status LED:
LED3 on the PCM circuit board.
Status
Off
There is no power applied to the circuit board or the board software is not executing its functions.
Green
The circuit board is operating normally.
Flashing Red
The circuit board has encountered a recoverable fault. Wait or cycle power to clear fault.
Red
The circuit board has encountered an unrecoverable fault.
OM-217 751 Page 30
Diagnosis
Diagnosis