Alpha Outback Energy GS7048E Manuel de démarrage rapide

Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} Alpha Outback Energy GS7048E. Alpha Outback Energy GS7048E 4 pages.

Setup and Programming
CAUTION: Equipment Damage
!
These procedures should be done by a qualified installer who is trained on programming inverter power systems.
Failure to set accurate parameters for the system could potentially cause equipment damage. Damage caused by
inaccurate programming is not covered by the limited warranty for the system.
IMPORTANT
Check the firmware revision of all OutBack devices before use. The Radian inverter and MATE3 system display may not
communicate or operate correctly unless their firmware is above a specified revision number.
For model GS7048E, the firmware must be revision 001.005.xxx or higher with a MATE3 revision of 002.010.xxx or higher.
For model GS3548E, the firmware must be revision 001.005.xxx or higher with a MATE3 revision of 002.017.xxx or higher.
Configuration Wizard
The MATE3 Configuration
Settings
Wizard allows quick setup of
Configuration Wizard
Configuration Wizard
Device Data Logs
parameters that apply to all
Event Logs
Firmware Update
systems. The Configuration
Wizard is reached from the
MATE3 Main Menu as
New Configuration
New Configuration
shown to the right.
Existing Configuration
Restore Configuration
The firmware revision of all
devices can be confirmed by
navigating from the MATE3
Main Menu as shown below.
New Configuration Initialized
Upgrades to the firmware
revision can be downloaded
Back
Continue
from the OutBack website
www.outbackpower.com or
AOE website www.alpha-
Off Grid
outback-energy.com .
Firmware Revision
System Type
Off Grid
System Voltage
48 VDC
Array Wattage
1000
Battery Type
FLA
Capacity
Back
Absorb Voltage
57.6 VDC
Settings
>>
Float Voltage
54.4 VDC
Configuration Wizard
Settings
>>
Equalize Voltage
60.0 VDC
Device Data Logs
>>
Re-Float Voltage
44.0 VDC
Event Logs
>>
Firmware Update
>>
Back
AC Output Voltage 230 VAC
System
System
>>
AC Phase
Single
Inverter
>>
AC Input Breaker Size 50 A
Charge Controller
>>
Maximum Output Load
30 A
Battery Monitor
>>
MATE3
>>
Back
Generator Installed
Y
System Information
>>
Generator Type
AC
Save / Store Information
>>
Generator Start
Manual
Firmware Version
>>
AUX Output Device Port 1
Date and Time
>>
LCD Display
>>
Back
Note: See the MATE3
manual for details on
MATE3
002.017.018
generator control.
1:
GS7048E 001.005.002
2:
GS7048E 001.005.002
If FN-DC is installed...
Shunt A
Connection
Inverter
S
This advances the display to the
Setup Complete screen.
Back
C
This advances the display to the
Setup Complete screen if the
Shunt B
Connection
Charge Controller
FLEXnet DC is not installed. If the
FLEXnet DC is installed, the display
Back
advances to the Shunt screens.
Shunt C
Connection
Charge Controller
Back
900-0159-01-00 REV C.vsd\Page-1\2015-09-30
>>
>>
Grid Tied
Backup
>>
>>
>>
System Type
Grid Tied
System Type
System Voltage
48 VDC
System Voltage
Array Wattage
1000
Array Wattage
Battery Type
FLA
Capacity
500 Ah
Battery Type
>>
Back
Continue
Back
>>
>>
Absorb Voltage
57.6 VDC
Time 1.0
Absorb Voltage
Float Voltage
54.4 VDC
Time 1.0
Float Voltage
Equalize Voltage 60.0 VDC
Time 3.0
Equalize Voltage
Re-Float Voltage 44.0 VDC
Re-Float Voltage
Back
Continue
Back
AC Output Voltage 230 VAC
AC Output Voltage 230 VAC
AC Phase
Single
AC Phase
AC Input Breaker Size 50 A
AC Input Breaker Size 50 A
Maximum Output Load
30 A
Maximum Output Load
Back
Continue
Back
Generator Installed
N
Generator Installed
Generator Type
AC
Size
5.0 kW
Generator Type
Generator Start
Manual
Generator Start
AUX Output Device Port 1
AUX Output Device Port 1
Back
Continue
Back
500 Ah
Continue
Period 1 Enable
N
Weekday Use
0:00
Drop 0:00
Weekend Use
0:00
Drop 0:00
Time
1.0
Time
1.0
Back
Continue
Back
Time
3.0
Continue
Period 2 Enable
N
Weekday Use
0:00
Drop 0:00
Back
Continue
Back
Continue
Period 3 Enable N
Weekday Use
0:00
Drop 0:00
Size
5.0 kW
Back
Back
Continue
Continue
C
Mode Disabled
Mode Disabled
Grid Connect
48.0 VDC
Delay 60 Min
Grid Connect
Grid Disconnect
52.0 VDC
Delay 60 Min
Grid Disconnect
Grid Connect SOC 60%
Disconnect SOC 95%
Grid Connect SOC 60%
Back
Continue
Back
C
If FN-DC is installed...
If FN-DC is installed...
Shunt A
Connection
Inverter
Continue
Back
Continue
Back
Shunt B
Connection
Charge Controller
Continue
Back
Continue
Back
Shunt C
Connection
Charge Controller
Continue
Back
Continue
Back
S
S
Quick Start Guide
WARNING: Fire/Explosion Hazard
Do not place combustible or flammable materials within 3.7 m (12 feet) of
the equipment. This unit employs mechanical relays and is not ignition-
protected. Fumes or spills from flammable materials could be ignited by sparks.
WARNING: Personal Injury
Use safe lifting techniques and standard safety equipment when working with
this equipment.
IMPORTANT:
Clearance and access requirements may vary by location. Maintaining a 90-cm
(36") clear space in front of the system for access is recommended.
Consult local electric code to confirm clearance and access requirements
for the specific location.
Backup
Radian Inverter/Charger
48 VDC
1000
FLA
Capacity
500 Ah
Continue
57.6 VDC
Time
1.0
54.4 VDC
Time
1.0
60.0 VDC
Time
3.0
MATE3
44.0 VDC
Continue
System
Display and
Controller
Single
30 A
Continue
N
AC
Size
5.0 kW
Manual
Continue
Period 1 Enable
N
Weekday Use 0:00
Drop 0:00
Weekend Use 0:00
Drop 0:00
Continue
Period 2 Enable
N
Weekday Use 0:00
Drop 0:00
Continue
Period 3 Enable
N
Weekday Use 0:00
Drop 0:00
HUB 10.3
Continue
Communications
Manager
48.0 VDC
Delay 60 Min
52.0 VDC
Delay 60 Min
Disconnect SOC 95%
Continue
C
GS Load
Center
(GSLC)
Shunt A
Connection
Inverter
Continue
Shunt B
Connection
Charge Controller
Continue
Shunt C
Connection
Charge Controller
Continue
S
FM80 Charge
Controllers
(x2)
Worldwide Corporate Offices
Headquarter Germany
Eastern Europe
France and Benelux
Hansastrasse 8
D-91126 Schwabach
Tel: +49 9122 79889 0
Middle East
Spain
Fax: +49 9122 79889 21
Alpha and Outback Energy GmbH reserves the right to make changes to the products and information contained in this document without notice. Copyright © 2020 Alpha and Outback Energy GmbH. All
Rights reserved.
www.alpha-outback-energy.com
For more information please visit
RADIAN Series
Major Components
Radian System Products
GS7048E
Inverter/Charger
GS3548E
GSLC175-PV-230
GS Load Center
GSLC175PV1-230
(both depicted)
MATE3 depicted
System Display
(with FW-MB3
and Controller
mounting bracket)
Optional OutBack Components
Communications
HUB10.3 depicted
Manager
FLEXmax 80 depicted
Charge Controller
(with FW-CCB2
mounting bracket)
PV Combiner Box
PV12 depicted
Remote Temperature Sensor (RTS)
FLEXnet DC Monitor (FN-DC)
Battery Bank
EnergyCell depicted
Customer-Supplied Components
Utility Grid or
AC Source
AC Generator
Main Electrical Panel (or overcurrent
device for the AC source)
Electrical Distribution Subpanel
(Load Panel)
Photovoltaic (PV) Array
IMPORTANT:
Not intended for use with
life support equipment.
Masters of the Off-Grid.™
First Choice for the New Grid.
Russia
Africa