ABB ControlMaster CMF Manuel - Page 4
Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} ABB ControlMaster CMF. ABB ControlMaster CMF 16 pages. Fieldmount universal controller/indicator
Specification
Mechanical data
Protection
IP66 / NEMA 4X
Dimensions
Height – 194 mm (7.64 in) minimum (excluding glands)
Width – 214 mm (8.42 in) – excluding glands
Depth – 98 mm (3.85 in) door closed – minimum (excluding
fixing brackets)
Weight – 1.5 kg (3.3 lb)
Materials of construction
Glass-filled polycarbonate
Weight
1.5 kg (3.3 lb).
Electrical
Power supply ranges
100 to 240 V AC max., 50 / 60 Hz ± 10 %
(90 to 264 V AC, 45/65 Hz)
Power consumption
25 W max.
Inputs / Outputs
Analog inputs
2 optional
Analog outputs
2 optional
Galvanically isolated from the rest of the circuitry, 500 V for
1 minute. Range-programmable source and range 0 to 22 mA,
maximum load 750 @ 20 mA
Relay outputs
4 standard, 2 optional
Fully-programmable. Contacts rated at 5A @ 110 / 240 V.
Standard relays are changeover.
Optional relays are normally closed (N/C).
4
Digital inputs / outputs
6 standard, user-programmable as input or output
Minimum input pulse duration: 125 ms
Input:
— Volt-free
(contact open > 10 M, contact closed < 100 k
— 24 V DC
(1-signal 15 to 30 V, 0-signal –3 to 5 V
— TTL
(low: 0 to 0.8 V / high: 2 to 5 V
— Conforms to IEC 61131-2
Output:
— Open collector
— 30 V, 100 mA max. switched
— Conforms to IEC 61131-2
Update rate:
— 125 ms
Environmental data
Ambient operating temperature:
0 to 55 ºC (32 to 131 ºF)
Ambient operating humidity:
Up to 95 % RH non-condensing
Storage temperature:
– 20 to 70 °C (–4 to 158 °F) without sensor
0 to 55 °C (41 to 131 °F) with sensor
Approvals, certification and safety
uULus
General safety
EN61010-1
Pollution Degree 2
Insulation Class 1
EMC
Emissions & immunity
Meets requirements of IEC61326 for an industrial environment
CI/CMF160/310–EN Rev. C