Acuity Brands Lighting Lithonia Lighting FML4W Wrap Manuel d'installation - Page 4
Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Acuity Brands Lighting Lithonia Lighting FML4W Wrap. Acuity Brands Lighting Lithonia Lighting FML4W Wrap 10 pages.
DIFFUSION LENS CLEANING:
Use a soft cloth and water to clean the lens. Avoid strong chemicals.
Mild soap or detergent combined with water may also be used, be sure to fully rinse lens with clean water.
Allow lens to air dry before reinstalling.
USE OF ADJUSTABLE LUMEN OUTPUT (ALO) – (IF LUMINAIRE IS EQUIPPED WITH THIS OPTION):
WITH POWER OFF and the lens removed from fixture (either before or after the fixture is installed on ceiling)
Use a ¼ inch flathead screwdriver to adjust the central knob of the lumen output device.
Follow the instructions on the label in the fixture, shown above, or consult table above for output settings.
Leave ALO at setting 8 (to provide maximum dimming range) if using 0-10V dimming below.
0-10V DIMMING – (IF LUMINAIRE IS EQUIPPED WITH THIS OPTION):
Purple and Grey wires for low voltage 0-10V control are provided in light fixtures with that option -
DO NOT CONNECT PURPLE OR GREY WIRES TO LINE VOLTAGE
If unfamiliar with 0-10V wiring, contact a qualified electrician.
A ½ inch knockout (KO) is provided to run these wires out of the light fixture to connect to 0-10V controls -
While fixture is on floor or a stable surface (not installed), use screwdriver to knock out ½ KO in housing.
Pliers may be necessary to bend knockout several times to remove.
MAKE SURE POWER IS OFF
Route the wires through KO and make connection to low voltage (0-10V) controls outside of fixture.
Pre-cut insulation on ends of purple and grey wire will need to be removed before making connections (wire nuts not included).
If using with a 0-10V wall dimmer, follow installation and use instructions that are provided with the dimming wall switch.
Leave the insulation ends on the purple and grey wires unless they will be used for 0-10V dimming. If insulation is removed, prevent contact with metal fixture housing by individually
capping the purple and grey wires with a wire nut (not included). Do not tie these wires together or fixture will be in constant dimmed output.
U815355
LED IMPORTANT SAFETY INSTRUCTIONS
ADJUSTMENT
KNOB
! PLEASE RETAIN THESE INSTRUCTIONS !
INSTALLATION INSTRUCTIONS
Setting
Approx. Wattage %
8
100%
7
100%
6
98%
5
88%
4
78%
3
66%
2
55%
1
43%
PURPLE/GREY
0-10V WIRES
½" 0-10V
KNOCKOUT
Approx. Lumen %
100%
100%
98%
89%
80%
70%
58%
46%
4 of 10