F14# Print PIN-code overview
By activating function 14 the systemmanager (Notice: only the systemmanager, with code number 98 (standard
445566!) can print an overview of all programmed Pin-codes via the printermodule.
Push the keys <?> <1> <4> <#> followed by a PIN-code of level 4 or 5.

F17# Testing the batter(y)(ies)

The control panel and possible linked expansionprints have been equipped with batteries. The system will keep in
function for several hours after powerloss. The batteries will function several years. The batteries are tested
automatically, but it is possible to test them manually with funktion 17.
Push the keys <?> <1> <7> <#> followed by a PIN-code of level 4 or 5.
On the display appears the message:
Batteries are
being tested.
This message stays on the screen for a few seconds. If all batteries are O.K., the text disappears. If batteries are
wrong a text on the screen will appear.

F19# Test outputs

Normally this function will be executed by the installing company only during the yearly check of the installation.
This test function is used to turn on and off the outputs, e.g. the siren, to check if all outputs are functioning
correctly. Use this function only after consulting the installing company.
If e.g. output 9 is used to active the indoor siren (loudspeaker) then this output can be tested as follows:
Push the keys <?> <1> <9> <#> followed by the main operator (supervisor) code.
The display will show:
Test output
number: -
Enter now <9> to activate output 9 (siren output) followed by <#>. The display will show:
Test output
number: 9
ON
Press <*> to turn off output 9 again. Enter another output number to test or press <*> for the second
time to leave this function.

F20# Display open zones

Function 20 to display open zones is available since september 1996. This function can be executed by all users.
If this function is executed, the control panel will display all zones that are open, one by one, except zones that
are allowed to be open at the time of arming. So the magnet contact at the frontdoor will never be shown as a
open zone, because this door is allowed to be opened at the moment of arming.
If some zones are open, e.g. zones 3 (living room) and 4 (computer room), then the display will show:
zone 03 is open
living room
zone 04 is open
computer room