AMCI DC60 Panduan Pengguna - Halaman 18

Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Konverter Media AMCI DC60. AMCI DC60 20 halaman. Multi-turn analog output duracoder

W
P
IRE
OWER AND
2.2 Connector Location and Pinout (continued)
2.2.1 Connector Pinout (continued)
Pins 4 and 6: No Function:
used, these pins should be tied to DC Return (pins 2 and 8) for normal operation to prevent them from picking
up any electrical noise in the environment.
Pin 5: Analog Output:
Pin 7: Direction Control:
put. The default is CW increasing output when looking at the shaft. If you are fabricating a custom cable and
want CW increasing output, this pin can be left open or attached to +DC Power Input (pin 1). Connecting this
pin to DC Return (pins 2 or 8), forces the output to increase with CCW rotation. If using a molded cordset,
connect the wire on this pin to either +DC Input Power or DC Return for normal operation. Do not leave the
wire floating.

2.2.2 Right Angle Cable Exit Direction

When designing a mounting solution for the DC60, be aware of the cable exit direction when using right
angle mating connectors. Figure 2.1 above shows the direction of the cable when using AMCI, TRUCK, or
Phoenix Contact cordsets.

2.2.3 Mating Connectors and Cordsets

AMCI offers the following mating connector and cordsets that mate with the NR60 power connector. Note that
the power connector will mate with any connector or cordset that follows the M12, 4 pin, A-coded standard.
AMCI #
MS-37
CNFL-5M

2.3 Sample Wiring Diagram

The diagram below shows how to wire a DC60 encoder using the CNFL-5M cable from AMCI.
1
2
7
3
8
4
6
5
M12 Connector
Female, A-coded, 8-pin
View from back of connector
18
I/O
These pins can be left open if you are fabricating a custom cable. If a cordset is
This pin is the analog output and it is referenced to DC Return (pins 2 and 8).
This pin controls which direction the shaft must rotate in to increase the analog out-
Description
Screw terminal connections. 6 to 8 mm dia. cable. 20 AWG max.
Straight, IP67 rated when properly installed.
Molded cordset. 5 meters in length.
Straight M12 8 pin A-coded to flying leads 
IP67 rated when properly installed.
Table 2.1 Compatible Connectors and Cordsets
AMCI CNFL-5M Cable
+DC Power Input
DC Return
Preset To Zero
No Function
No Function
Direction Control
Analog Out
DC Return
Notes:
Color code is for the CNFL-5M cable available from AMCI.
The Direction Control pin should be tied to +DC Power for CW increasing output or DC Return for CCW increasing output.
The Preset to Zero pin should be attached to +DC Power Input for normal operation.
No Function pins should be grounded for normal operation.
For voltage output, if input impedance exceeds 10 kohm, consider installing a 10 kohm resistor to improve noise immunity.
Figure 2.2 Sample Wiring Diagram
WHT
BRN
GRN
YEL
GRY
PNK
BLU
RED
DRAIN
ADVANCED MICRO CONTROLS INC.
Analog DC60 User Manual
POWER SUPPLY
INPUT DEVICE
CHASSIS
-IN
GND
+Vdc
-Vdc
GND
+IN