Astronergy CHSM6612M/HV Manual - Halaman 14

Jelajahi secara online atau unduh pdf Manual untuk Peralatan Industri Astronergy CHSM6612M/HV. Astronergy CHSM6612M/HV 19 halaman. Crystalline silicon pv
Juga untuk Astronergy CHSM6612M/HV: Panduan Instalasi (12 halaman), Panduan Instalasi (18 halaman), Panduan Instalasi (19 halaman)

Astronergy CHSM6612M/HV Manual
2094*1038*35
2094*1038*30
2256*1133*35
2278*1134*35
2278*1134*30
6

Electrical Installation

6.1

Electrical characteristics

Module electrical ratings are measured under Standard
Test Conditions(STC: 1000W/m
spectrum and a cell temperature of 25°C). Please refer
to the datasheet or the product nameplate for the main
electrical characteristics, maximum system voltage and
tolerance of Isc, Voc and Pmpp.
Under certain conditions, the output current and/or
voltage of the PV module may be higher than the value
under standard testing conditions. Therefore, the value
of Isc marked on the module should be multiplied by
1.25, and Voc on the module should be multiplied by a
correction factor (see table 3 below) when determining
component ratings and capacities. Depending on your
local regulations, an additional 1.25 multiplier for the
Isc(giving a total multiplier of 1.56) may be applicable
when sizing conductors and fuses.
14
-2400Pa
-2400Pa
+5400Pa
---
-2400Pa
+5400Pa
+2400Pa
-2400Pa
-2400Pa
+5400Pa
---
-2400Pa
+5400Pa
---
-2400Pa
2
irradiance, AM1.5
Installation scope
400±50mm
+5400/-2400Pa
Installation scope
350-400mm
+5400/-2400Pa
Installation scope
400~450mm
+5400/-2400Pa
Installation scope
400~450mm
+2400/-2400Pa
Installation scope
400~500mm
+5400/-2400Pa
Installation scope
429~449mm
Table 3 Correction factor of Voc at low temperature
Lowest Estimated Ambient
Temperature(℃)
24 ~ 20
19 ~ 15
14 ~ 10
9 ~ 5
4 ~ 0
-1 ~ -5
-6 ~ -10
-11 ~ -15
-16 ~ -20
-21 ~ -25
-26 ~ -30
-31 ~ -35
-2400Pa
+Bumper
---
---
+1800Pa
---
-1800Pa
+Bumper
+1800Pa
---
-1800Pa
+Bumper
+1800Pa
---
-1800Pa
Correction factor
1.02
1.04
1.06
1.08
1.10
1.12
1.14
1.16
1.18
1.20
1.21
1.23