Advanced Electronics MXPro4 Mxp-008F Manual - Halaman 7

Jelajahi secara online atau unduh pdf Manual untuk Relai Advanced Electronics MXPro4 Mxp-008F. Advanced Electronics MXPro4 Mxp-008F 10 halaman. Relay output cards

Advanced Electronics MXPro4 Mxp-008F Manual

2.1 May Silence:

If this parameter is ticked, the relay will behave in a similar manner to a sounder circuit output. It will energise as
defined by their "Output Group" setting and de-energise when the "Silence" key is pressed.

2.2 Inverted Output:

If this parameter is ticked, the
energised in its quiescent state and de-energised when its "Output Group" setting is activated.

2.3 May Walk Test:

If this parameter is ticked, the relays assigned with this parameter will be allowed to energise when a "Walk Test"
with ring bells option is enabled.
The relay will energise for a short time, along with the bells / sounders, when a walk test alarm is generated.

2.4 Investigation:

If this parameter is ticked, the relay will follow the programmed output stage 1 delay timer and delay its operation
while the cause of the alarm is investigated.
www.acornfiresecurity.com
relay will behave in a manner similar to a "Fault" relay output and will be normally
www.acornfiresecurity.com
7