Anderson LD Series Buku Petunjuk - Halaman 15

Jelajahi secara online atau unduh pdf Buku Petunjuk untuk Pemancar Anderson LD Series. Anderson LD Series 18 halaman. Level transmitter

2.8 CONTROLLER TUNING

2.8 CONTROLLER TUNING
2.8 CONTROLLER TUNING
2.8 CONTROLLER TUNING
2.8 CONTROLLER TUNING
As depicted in Figure 2-1, the typical application utilizes the signal from the transmitter to
interface with a programmable controller. In turn, this unit typically sends an output that is used
to throttle a feed valve. For actual P (Proportional), I (Integral) and D (Derivative) tuning informa-
tion, please consult the instruction manual provided with the controller. Some general control-
ler setup guidelines are as follows:
" WC = (Inches height X specific gravity of product)
1.
The transmitter is calibrated in " WC. If the vessel is less than 30" WC height, the
default calibration for the transmitter remains at 30" WC. Be sure to set the
controller accordingly.
2.
Be sure that either the controller is capable of providing proper loop power, or that
an external supply is utiized. Refer to the controller instruction manual for guide-
lines on proper wiring of an internal supply. Utilize Figure 2-3 as a reference to be
sure that all loop polarities are wired correctly.
3.
On a typical controller, the following are the basic requirements to perform initial
startup. Again, refer to the actual manual for detailed instructions.
a. Specify a 4-20 mA input type to match the output of the transmitter.
b. Be sure any configuration switches internal to the controller are properly set.
c. Be sure wiring of loop/power source is correct.
d. Enter a "Lower" and "Upper" operating limit - typically 0 - 100%.
P
15
AGE