Diesel Generators
The diesel generator is started by the GSCM in either automatic or manual mode. A field installed relay that will handle the
glow plug current is needed if not already installed on the engine. A fuel control solenoid is connected to the K3 (ignition)
relay terminals. decompression solenoid furnished with the generator must be wired to K4 (shutdown) relay to energize on
shutdown.
Automatic Generator Powered AC Pump
In this application the GSCM is connected to a pressure or level switch into the battery sense terminals. To make the
appropriate cut-in and cut-out adjustments. See AUTOMATIC STARTING FOR BATTERY CHARGING section: 9. The cut-in and
cut-out adjustments must be set at the maximum for the switched input auto start mode to operate. See AUTOMATIC
STARTING FOR BATTERY CHARGING section: 9 & 4:9. The K5 (load) relay energizes the pump contactor.
www.atkinsonelectronics.com
800.261.3602
13
Circuit Board Division
Revised 09/18