Atkinson Electronics A0217 Manual - Halaman 14

Jelajahi secara online atau unduh pdf Manual untuk Unit Kontrol Atkinson Electronics A0217. Atkinson Electronics A0217 16 halaman. Generator start control module

Atkinson Electronics A0217 Manual

Fuel Powered Pump

A pressure or level switch starts a direct engine driven pump similar to application 5. The K5 (load transfer) relay is used to
energize the pump unloader valve closing when the engine is running. The unloader valve bleeds off the pump pressure when
de-energized. The standard GSCM "out of the box" looks for a minimum 100V AC frequency input signal. Order a special low
voltage generator frequency input version for 12V alternator applications. GSCM, 12V ALT 255 Hz. See AUTOMATIC STARTING
FOR BATTERY CHARGING section: 9 & 4:9.

Generator Powered Air Conditioner

The room thermostat (should be line voltage slow action type to minimize short cycling) signals the generator to start. The
GSCM K5 (load transfer) relay starts the air conditioner after the generator is running. When the thermostat is satisfied, it
opens the start signal to the GSCM. The air conditioner is instantly turned off by the K5 (load transfer) relay, however, the
generator continues to run during the cool down cycle for the period of time selected.
www.atkinsonelectronics.com
800.261.3602
14
Circuit Board Division
Revised 09/18