Baud rate
Baud rate options: 2400 4800 9600 19200 38400 (bps).
Default: 9600bps
From the Set-up menu, Use
Baud rate options.
E
Long press
The Baud Rate setting will flash. Use
choose Baud Rate.
Long press
E
return to the main menu.
Parity
Parity Options: NONE, EVEN, ODD.
Default Parity : EVEN
Note that if parity is set to ODD or EVEN, Stop Bits will be set
to 1 and cannot be changed.
From the Set-up menu, Use
Parity options.
E
Long Press
The Parity setting will flash. Use
Parity.
Example shows:
Set Parity: EVEN
And long press
Press
to return the main set up menu.
ESC
Connection
This meter is for
monitoring only
and can not be
connected to the
Autometers
Horizon Data
Monitoring System
to the next meter
Communications shield continuous
Dimensions
The meter is a 96 x 96 mm panel mounted meter with a depth of 70mm
The cut out hole for the panel meter is 92 x 92 mm.
PF Hz
P
and
to select the
MD
to enter the selection routine.
PF Hz
and
P
MD
for confirmation and then press
PF Hz
P
and
to select the
MD
to enter the selection routine.
PF Hz
and
P
to choose
MD
E
for confirmation.
to the next meter
Belden 9841 or Equal Cable Screened
Twisted pair with full Coax shielding
for RS 485 Modbus connection.
Red.....TX+
,
Black...TX-
96
62
98
The Q-180 series of meters are for monitoring
only and are not suitable for revenue collection.
The Q-180 series of meters has a different RS
485 Modbus Protocol and therefore cannot be
connected to the Horizon data monitoring
to
to
ESC
C.T. (Current Transformer)
C.T.2 (Current Transformer Secondary)
C.T. Rate (Current Transformer Primary)
,
Green...Shield
Example of meter set at 200/5 amp
Product development is continuous and Autometers Systems Limited reserves the
right to make alterations and manufacture without notice. Products as delivered may
therefor differ from the descriptions and illustrations in this publication
IMPORTANT NOTICE
system
From the main Set-up menu, Use
CT option.
Set C.T.2 secondary current input.
Options: 5A or 1A
Default CT2: 5A
Long press
to enter the CT2 routine.
E
E
Press
for 2s, the CT2 setting will flash.
PF Hz
Use
and
P
to choose CT2 with 5A or 1A.
MD
Press
to return to the main menu.
ESC
To program the current ratio in the meter simply enter the
primary current.
eg. if you require the meter to be set at 200amp program
the numbers to be 0200.
Long press
E
to enter the CT Rate routine.
Press
E
for 2s, the CT rate setting will flash.
Use
PF Hz
and
P
to choose the first digit of the CT value.
MD
Press
E
to move the cursor to the right. When you have
entered the desired setting long press
confirmation and then press
to return to the main
ESC
menu.
Example of how the display should look for a meter
programmed to 200/5 amp.
Autometers Systems Ltd.
4B Albany Road, Chorlton-cum-Hardy
Email: [email protected]
Phone: 00(44) 0161 861 9056
www.autometers.co.uk
PF Hz
and
to select the
P
MD
E
for