Autonics KT-502H Panduan Memulai Cepat - Halaman 2

Jelajahi secara online atau unduh pdf Panduan Memulai Cepat untuk Alat Ukur Autonics KT-502H. Autonics KT-502H 4 halaman.

Autonics KT-502H Panduan Memulai Cepat
Dimensions
● Mounting bracket
Input Type And Range
Input type
Input range(℃)
DPt100Ω
DPt500Ω
DPt1000Ω
Cu50Ω
RTD
Cu100Ω
Ni100Ω
Ni500Ω
Ni1000Ω
Resistance
Resistance (Ω)
transmitter
B
(PtRh30-PtRh6)
E(NiCr-CuNi)
J(Fe-CuNi)
K(NiCr-Ni)
Thermocouple
N(NiCrSi-NiSi)
R(PtRh13-Pt)
S(PtRh10-Pt)
T(Cu-CuNi)
Analog
Voltage
83
55
94
Input range(℉)
200 to 850
328 to 1562
200 to 250
328 to 482
200 to 250
328 to 482
50 to 150
58 to 302
50 to 150
58 to 302
60 to 180
76 to 356
60 to 180
76 to 356
60 to 150
76 to 302
0 to 400Ω
-
0 to 2000Ω
0 to 1820
32 to 3308
270 to 1000
454 to 1832
210 to 1200
346 to 2192
270 to 1372
454 to 2501.6
270 to 1300
454 to 2372
50 to 1768
58 to 3214.4
50 to 1768
58 to 3214.4
270 to 400
454 to 752
10 - 75mV
100 - 100mV
-
100 - 500mV
100 - 2000mV
Temperature Transmitter
142
2-(1/2 14NPT)
Mounting bracket
Connections
HART Communicator
1
2
3
4
A
B
b
RTD
mV
+
-
TC
+
-
● Opening cover
(unit: mm)
Indicator
Recorder
DCS
Controller
Power
Supply
Min. 250Ω
5
6
-
+
Power supply
10.5-45VDC
To open the cover,
unscrew the M3×6L
headless bolt using a 1.5
hexagon wrench and rotate
the cover.
A. Recorder
B. Indicator
C. Converter
D. Controller
E. Thyristor
unit
F. Pressure
transmitter
G. Temp.
transmitter
H. Accessories
KT-502H
G-3