Preset Setting
■ Setting method
• Setting name and value are cross-displayed in SV display part.
1. Set the operation mode in P-2 OUT operation mode.
2. Enter the preset setting mode by pressing [M] key from RUN mode.
3. Select the setting item by [M] key and change the preset by [▼] or [▲] key.
4. Press [M] key to save setting or no key input over 60 sec not to save setting and
return to RUN mode. (except forced output control mode)
■ Preset setting by operation mode
Operation mode
Preset
Pressure
detection level 1
Hysteresis level 1 HYS1 Min. display pressure ≤ HYS1 < ST1
Hysteresis
Pressure
HYsM
detection level 2
Hysteresis level 2 HYS2 Min. display pressure ≤ HYS2 < ST2
Pressure
detection low
limit 1
Pressure
detection high
Window
limit 1
comparison
Pressure
output
WIN
01)
detection low
limit 2
Pressure
detection high
limit 2
Pressure
detection level 1
Hysteresis level 1 HYS1 Min. display pressure ≤ HYS1 < ST1
Hysteresis-
Pressure
Window
detection low
comparison
HY-W
limit
output
02)
Pressure
detection high
limit
Pressure level 1
Auto
Pressure level 2
sensitivity
setting
AUTO
Pressure
detection level
Forced output
fOUT -
control
04)
01) Hysteresis: 1 (min display interval, fixed)
02) ST1 = HYS1, actual hysteresis is 1 (min. display interval)
03) When error appears, check setting conditions and set proper setting values.
04) [Option external input model] Forced output does not support external input terminal.
■ Precaution
• The preset value (default) of the changed operation mode is set when changing P-2
OUT operation mode setting.
• Preset value is converted as the changed unit automatically when changing P-1
Display unit setting.
• Preset is reset when changing P-9 External input terminal setting.
■ Default setting value
Operation mode
Preset
ST1 -50.0
HYS1 0.0
Hysteresis
ST2 -50.0
HYsM
HYS2 0.0
LO-1 0.0
Window
HI-1 -50.0
comparison
LO-2 0.0
output
WIN
HI-2 -50.0
ST1 -50.0
Hysteresis-
HYS1 0.0
Window
comparison
LOW 0.0
HY-W
output
HIGH -50.0
ST1 0.0
Auto
sensitivity
ST2 -50.0
setting
AUTO
SET -25.0
Forced output
fOUT -
control
Setting range
Min. display pressure < ST1 ≤ Max. display
pressure
ST1
Min. display pressure < ST2 ≤ Max. display
pressure
ST2
Min. display pressure ≤ LO-1 ≤ Max.
display pressure -(3 × Min display interval)
LO-1
LO-1 + (3 × Min display interval) ≤ HI-1 ≤
Max. display pressure
HI-1
Min. display pressure ≤ LO-2 ≤ Max.
display pressure - (3 × Min display interval)
LO-2
LO-2 + (3 × Min display interval) ≤ HI-2 ≤
Max. display pressure
HI-2
Min. display pressure < ST1 ≤ Max. display
pressure
ST1
Min. display pressure ≤ LOW ≤ Max.
display pressure - (3 × Min display interval)
LOW
Low + (3 × Min display interval) ≤ HIGH ≤
Max. display pressure
HIGH
Min. display pressure ≤ ST1 ≤ Max. display
pressure - 1% of rated pressure
ST1
ST1 + 1% of rated pressure ≤ ST2 ≤ Max.
03)
display pressure
ST2
(ST1+ST2)
Auto setting
SET=
2
• Manual setting is possible by [▼] or [▲]
SET
key.
• Manual ON/OFF for OUT1/2 is possible by
-
[▼] or [▲] key.
Negative
Static
0.1 kPa
0.1 kPa
1 kPa
50.0
500
0.0
0
50.0
500
0.0
0
0.0
0
50.0
500
0.0
0
50.0
500
50.0
500
0.0
0
0.0
500
50.0
0
0.0
0
50.0
500
25.0
250
Output Operation Mode
Change the output operation mode to change pressure detection method.
ON:
■ Hysteresis
• Set the hysteresis for pressure detection
directly.
• Setting: Pressure detection level (ST1,
ST2), Hysteresis (HYS1, HYS2)
Pressure
H
ST2 / HYS2
H
ST1 / HYS1
OUT1 N.O.
ST1 / HYS1
OUT1 N.C.
ST1 / HYS1
OUT2 N.O.
ST2 / HYS2
OUT2 N.C.
ST2 / HYS2
■ Hysteresis - Window
comparison output
• It is available both hysteresis mode
and window comparison output mode
operations.
• Setting: Pressure detection level (ST1),
Hysteresis (HYS1), High limit (HIGH), Low
limit (LOW)
Pressure
A
HIGH
A
LOW
ST1
HYS1
OUT1 N.O.
ST1 / HYS1
OUT1 N.C.
ST1 / HYS1
OUT2 N.O.
LOW / HIGH
OUT2 N.C.
LOW / HIGH
■ Forced output control
• It displays the present pressure with
forcibly holding comparing output OFF
regardless of setting value.
• Manual ON/OFF for OUT1/2 is possible
by [M], [▼] or [▲] key during forced
output control operation.
[M]
[▼]
[▼]
OUT1
[▲]
Compound
0.1 kPa
OUT2
50.0
-50.0
50.0
-50.0
-50.0
50.0
-50.0
50.0
50.0
-50.0
-50.0
50.0
-50.0
50.0
0.0
OFF:
H: Hysteresis A: Min display interval
■ Window comparison output
• It detects pressure at the desired range.
• Hysteresis is fixed as min. display
interval.
• Setting: High limit (HI1, HI2), Low limit
(LO1, LO2)
Pressure
HI2
LO2
HI1
LO1
Time
OUT1 N.O.
LO1 / HYS1
OUT1 N.C.
LO1 / HYS1
OUT2 N.O.
LO2 / HYS2
OUT2 N.C.
LO2 / HYS2
■ Auto sensitivity setting
• This function is to set the proper position
(SET) automatically by applied pressure
from two positions (ST1, ST2).
(ST1+ST2)
SET=
• Hysteresis is fixed as min. display
interval.
Pressure
ST2
SET
ST1
Time
OUT2 N.O.
SET
OUT2 N.C.
SET
OUT1 N.O.
ST1/ST2
OUT1 N.C.
ST1/ST2
[M]
[▼]
Time
[▲] [▲]
Time
A
A
A
A
Time
2
A
A
A
Time