Step-by-step
Add a suitable cleaner, such as MC5
5
to the system via the RapidFlush Filter
canisters.
If this has already been added, skip this
step.
Turn ON isolation valves on the
6
RapidFlush Filter. Re-fill and pressurise
the central heating system ensuring the
radiators are half-full. Check for leaks.
Turn on central heating system. Make
7
sure all radiator valves are fully open.
The radiators should be hot at the
bottom, cold at the top. Allow system to
reach temperature (over 70°C).
Turn off any bypass valves and all the
8
radiators, ensuring they are FULLY
closed. Leave the furthest radiator
open. With the system running, use
ADEY Vibraclean tool attached to an
SDS drill, set to hammer only mode with
no rotary action, agitate open radiator
for 15-20 seconds, along the bottom of
the radiator. Repeat process on each
radiator, moving from furthest away
radiator to radiator closest to the boiler.
Remember to monitor the MagnaCleanse throughout operation.
,
®
ON