Airflow Uno hab Panduan Petunjuk Pemasangan dan Pengoperasian - Halaman 14

Jelajahi secara online atau unduh pdf Panduan Petunjuk Pemasangan dan Pengoperasian untuk Sistem Pemanas Airflow Uno hab. Airflow Uno hab 16 halaman. Cavity wall decentralised mechanical ventilation with heat recovery unit
Juga untuk Airflow Uno hab: Petunjuk (2 halaman), Kit Instalasi (16 halaman), Panduan Pemeliharaan (2 halaman)

© Airflow - we reserve the right to make changes without prior notice
7.1
Wiring diagram SD-4
Operation with 8 x Unohab and 2 x Unohab PSF connected in parallel
Unohab: M1 - start cycle: supply
M7
3
Unohab PSF*
For 8 x Unohab
2 x Unohab PSF
should be connected in
parallel. (directly next to
.
each other or below
each other)
Unohab PSF*
1,5 mm²,
max. 4 m
Unohab CTRL
Operation with 4x Unohab and 1 x Unohab PSD or Operation
with 8 x Unohab and 2 x Unohab PSD connected in parallel
Unohab: M1 - start cycle: supply
M7
3
Unohab Unit
6 - GND
8 - + 12V
M5
M3
M1
10 - PWM Start Supply
11 - PWM Start Extract
3
3
3
6
Distributor
8
UP-Dose
+
230 V~
230 V~ /
12 V =
-
1)
UP-Dose
+
230 V~
230 V~ /
12 V =
-
2
UP-Dose
7
8 9 10 11
6
-
5
4
+
1 2
6 - GND
M5
M3
M1
8 - + 12V
10 - PWM Start Supply
11 - PWM Start Extract
3
3
3
6
Distributor
8
Unohab CTRL
UP-Dose
7
8 9 10 11
6
-
5
4
+
1 2
2
+ + - -
1,5 mm², max. 30 m
L N
14
Installation and Operating Instructions
Unohab: M2 - start cycle: extract
M6
M2
M4
3
3
10 11
- Recommended Cable J-Y (ST) Y 0.8 mm
- Maximum distance between Unohab CTRL and
Unohab motor: 30 m
- All motors connected to Distributor
- Max. distance from Unohab CTRL to Distributor:
4 m
Max. 4 m from Distributor
Unohab: M2 - start cycle: extract
M6
M2
M4
3
3
10 11
- Recommended Cable J-Y (ST) Y 0.8 mm
- Maximum distance between Unohab CTRL and
Unohab motor: 30 m
- All motors connected to Distributor
- Max. distance from Unohab CTRL to Distributor:
4 m Max. 4 m from Distributor
For 5-8 Unohab
+ + - -
2x Unohab PSD
connected in parallel
( side by side )
L N
230 V~
fig.23
M8
3
3
2
M8
3
3
2
SD-4