4. Electrical Connection
Model
SC997
SC998
⚠ WARNING: Power supply of heat pump must be disconnected before any operation.
Please comply with the following instruction to connect heat pump.
Step 1: Detach electrical side panel by a screwdriver to access electrical terminal block.
Step 2: Insert cable into heat pump unit port.
Step 3: Connect power supply cable to terminal block.
IV. Running Test

1. Inspection Before Running Test

a. Running test can begin after completing all installation;
b. Before running test, confirm below items and write √ in block;
● Correct unit installation □ ● Power supply voltage is the same as unit rated voltage □
● Correct piping and wiring
● Drainage and venting is unblocked and no water leaking
● Leakage protector is working
● Piping insulation is working □
c. All wiring and piping should be connected well and carefully checked, then fill water tank with water
before power is switched on;
d. Emptying all air within pipes and water tank, press "on-off" button on control panel to run the unit at
setting temperature;
e. Items need to be checked during running test:
 During the first running, unit current is normal or not;
 Each function button on control panel is normal or not;
 Display screen is normal or not;
 Are there any leakage in the whole heating circulation system ;
Power Supply Wires Size
Electricity Supply
220-240V~/50Hz
● Air inlet & outlet port of unit is unblocked
● Ground wire is connected correctly
9
Power Supply Wires
Cable Diameter
3G 1.5mm²
3G 1.5mm²
Specification
AWG 14
AWG 14