Miele DA 5428 W Petunjuk Pengoperasian dan Pemasangan - Halaman 37
Jelajahi secara online atau unduh pdf Petunjuk Pengoperasian dan Pemasangan untuk Kap Ventilasi Miele DA 5428 W. Miele DA 5428 W 48 halaman.
de Installation area (only d is required for recirculation operation). Wall or ceiling
area for the ducting cutout and for the electrical outlet. For recirculation
operation, only an electrical outlet needs to be installed.
Exhaust connection 6" (150 mm)
Distance between cooktop and ventilation hood (S)
Provided a larger distance is not given by the manufacturer of the cooktop,
follow the minimum safety distances between a cooktop and the bottom of the
hood.
Please also observe the information contained in the "IMPORTANT SAFETY
INSTRUCTIONS" section.
Cooking appliance
Electric Cooktops
Electric Barbeques and Fryers
Multiburner Gas Cooktops
≤ 43,000 BTU/hr (12.6 kW),
no burner > 15,000 BTU/hr (4.5 kW).
Multiburner Gas Cooktops
≤ 73,800 BTU/hr (21.6 kW),
no burner > 16,500 BTU/hr (4.8 kW)
Multiburner Gas Cooktops
> 73,800 BTU/hr (21.6 kW),
or one of the burners > 16,500 BTU/hr (4.8 kW)
Single Burner Gas Cooktops
≤ 20,500 BTU/hr (6 kW)
Single Burner Gas Cooktops
> 20,500 BTU/hr (6 kW)
≤ 27,600 BTU/hr (8.1 kW)
Single Burner Gas Cooktops
> 27,600 BTU/hr (8.1 kW)
Installation
Minimum distance S
Miele
appliance
24" (610 mm)
26" (660 mm)
26" (660 mm)
30" (760 mm)
30" (760 mm)
Not possible
26" (660 mm)
30" (760 mm)
30" (760 mm)
Not possible
Non-Miele
appliance
37