ABB ACS580-01 drives Panduan Instalasi dan Start-Up Cepat - Halaman 11
Jelajahi secara online atau unduh pdf Panduan Instalasi dan Start-Up Cepat untuk Peralatan Industri ABB ACS580-01 drives. ABB ACS580-01 drives 17 halaman. Frequency converter. nec types
Juga untuk ABB ACS580-01 drives: Manual (16 halaman), Panduan Instalasi dan Start-Up Cepat (17 halaman)
- 1. Install the Drive on the Wall
- 2. Remove the Cover(S)
- 3. Connection Procedure
- 4. Connect the Control Cables
- 5. Start up the Drive
- 6. Fieldbus Communication
- 7. Warnings and Faults
- 8. Terminal Data for the Power Cables
- 9. Ambient Conditions
- 10. Safe Torque off (Sto)
- 11. Related Documents
- 12. Declarations of Conformity
Overview and connection diagrams for connecting the drive to the fieldbus are shown below.
X5
Termination OFF
Bias OFF
Drive
Drive control
unit
•
Tie shield conductors together at the drive. Do not terminate at SCR.
•
Terminate the shield only at terminal "G" (ground) in the automation controller.
•
Terminate DGND conductor at terminal "R" (reference) in the automation controller.
13. Install optional modules, if included in the delivery
14. Install the cover(s)
The cover installation procedure is the opposite of the removal procedure. Refer to
install the side plates shown in
15. Start up the drive
WARNING! Before you start up the drive, make sure that the installation is completed. Make sure also that it is safe
to start the motor. Disconnect the motor from other machinery, if there is a risk of damage or injury.
Use the control panel to do the start-up procedure. The two commands at the bottom of the display show the functions of
the two softkeys
and
depending on the context. Use the arrow keys
active view. Key
shows a context-sensitive help page.
?
1.
Power up the drive. Make sure that you have the motor name plate data available.
2.
The First start assistant guides you through the first start-up.
The assistant begins automatically. Wait until the control panel shows
the language selection screen.
Select the language you want to use and press
Note: After you select the language, it takes a few minutes for the
control panel to wake up.
3.
Select Start set-up and press
X5
Termination OFF
Bias OFF
Drive
X1
X5
1
29
30 31
Connection procedure
before you install the cover.
located below the display. The commands assigned to the softkeys are different
,
,
(Next).
Fieldbus controller
1)
Termination ON
Fieldbus
X5
Termination ON
2)
Bias ON
Drive
Automation controller
Remove the cover(s)
and
to move the cursor or change values depending on the
(OK).
1) The devices at both ends
on the fieldbus must have
termination set to ON.
2) One device, preferably at
the end on the fieldbus,
must have bias set to ON.
1)
-
G
R
+
. In frames R6...R9,
11