ABB ACS580-01 drives Panduan Instalasi dan Start-Up Cepat - Halaman 12
Jelajahi secara online atau unduh pdf Panduan Instalasi dan Start-Up Cepat untuk Peralatan Industri ABB ACS580-01 drives. ABB ACS580-01 drives 17 halaman. Frequency converter. nec types
Juga untuk ABB ACS580-01 drives: Manual (16 halaman), Panduan Instalasi dan Start-Up Cepat (17 halaman)
- 1. Install the Drive on the Wall
- 2. Remove the Cover(S)
- 3. Connection Procedure
- 4. Connect the Control Cables
- 5. Start up the Drive
- 6. Fieldbus Communication
- 7. Warnings and Faults
- 8. Terminal Data for the Power Cables
- 9. Ambient Conditions
- 10. Safe Torque off (Sto)
- 11. Related Documents
- 12. Declarations of Conformity
4.
Select the localization you want to use and press
5.
To complete the first start assistant, select the values and settings
when prompted by the assistant. Continue until the panel shows that
the first start is complete.
When the panel shows that the first start is complete, the drive is ready
for use. Press
(Done) to enter the Home view.
6.
The Home view shows the values of the selected signals.
7.
Make additional adjustments, for example macro, ramps and limits,
starting from the Main menu. Press
enter the Main menu.
Select Primary settings and press
With the Primary settings menu, you can adjust settings related to the
motor, PID, fieldbus, advanced functions and clock, region and display.
You can also reset logs, parameters, and the control panel Home view.
ABB recommends that you make at least these additional settings:
• Choose a macro or set start, stop and reference values separately
• Ramps
• Limits.
To get more information on the Primary settings menu items, press
to open the help page.
Fieldbus communication
To configure the embedded fieldbus communication for Modbus RTU, you must set at least these parameters:
Parameter
20.01 Ext1 commands
22.11 Ext1 speed ref1
26.11 Torque ref1 source
28.11 Ext1 frequency ref1
58.01 Protocol enable
58.03 Node address
(Menu) in the Home view to
(Select) (or
Setting
Description
Embedded
Selects fieldbus as the source for the start and stop commands when
fieldbus
EXT1 is selected as the active control location.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as speed reference 1. Use this parameter with the vector motor control
mode.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as torque reference 1. Use this parameter with the vector motor
control mode.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as frequency reference 1. Use this parameter with the frequency motor
control mode.
Modbus RTU
Initializes embedded fieldbus communication.
1 (default)
Node address. There must be no two nodes with the same node
address online.
(Next).
).
?
12