POWER REQUIREMENTS
This product requires a transformer capable of providing 24VAC power to the product. Use of a UL listed 24VAC
transformer is recommended.
To connect power, use the supplied two-position terminal plug. The output leads from the transformer should
be connected to the terminal plug. The terminal plug is then connected into the socket marked J1 on the PCB.
American Auto-Matrix recommends using 18AWG cable for power wiring.
Figure 1-5 Connecting Power to MATRIX Series Area Controller
WARNING: Do not share the power source for Aspect MATRIX Series MAX Area Controller with other
devices. Damage to the product as a result of improper power and wiring will void product
warranty.
LED INDICATION
The PCB of the product includes diagnostic LEDs, providing user feedback when power has been connected to
the device. When power is connected, all three of the LEDs should be illuminated. The power diagnostic LEDs
are located near port 1's terminal block switches.
Figure 1-6 Power LEDs on Aspect MATRIX Series Area Controller PCB