Cisco IC3000 Panduan Pemasangan Perangkat Keras - Halaman 22

Jelajahi secara online atau unduh pdf Panduan Pemasangan Perangkat Keras untuk Gerbang Cisco IC3000. Cisco IC3000 37 halaman. Industrial compute gateway
Juga untuk Cisco IC3000: Dokumentasi Produk (12 halaman)

Cisco IC3000 Panduan Pemasangan Perangkat Keras
Mounting the IC3000 in a Rack
4. Remove the device from the DIN rail.
Mounting the IC3000 in a Rack
The IC3000 can be mounted in a 19" cabinet/rack with the optional kit part number STK-RACK-DINRAIL=.
This kit includes a bracket and mounting screws.
Figure 4: Mounting Bracket
To install the IC3000 in a cabinet or rack, perform the following steps:
1. Install the bracket in the cabinet or rack using the 4 front screws included in the kit. Place the screws
through the mounting holes (#1).
2. Attach The device to the DIN rail built into the mounting bracket (#2) in the same manner as described
in
Installing the Cisco IC3000 Ground Connection
The device must be connected to a reliable earth ground. Install the ground wire in accordance with local
electrical safety standards.
• For NEC-compliant grounding, use size 16 AWG (1.5mm2) or larger copper wire and a ring terminal
• The ground lug is not supplied with the device. You can use either a single ring terminal or two single
WARNING: This equipment needs to be grounded. Use a green and yellow 16 AWG (1.5mm2) ground wire
to connect the host to earth ground during normal use. Statement242
WARNING: This equipment must be grounded. Never defeat the ground conductor or operate the equipment
in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority
or an electrician if you are uncertain that suitable grounding is available. Statement1024
WARNING: When installing or replacing the unit, the ground connection must always be made first and
disconnected last. Statement1046
WARNING: This equipment is intended to be grounded to comply with emission and immunity requirements.
Ensure that the device functional ground lug is connected to earth ground during normal use. Statement 1064
To install the ground connection, follow these steps:
Cisco IC3000 Industrial Compute Gateway Hardware Installation Guide
20
Installing a DIN Rail, on page
with an inner diameter of 1/4 in. (5 to 6 mm).
ring terminals.
Installing the Cisco IC3000 Industrial Compute Gateway
18.