Ratings, fuses and typical power cables
1) Typical motor power with no overload capacity (nominal use). The kilowatt ratings apply to most IEC 4-pole motors. The
horsepower ratings apply to most NEMA 4-pole motors.
2) For IEC installations, ABB recommends aR fuses. The gG fuses can be used for frames R3 and R6 if they operate rapidly
enough (max. 0.1 seconds). The operating time depends on the supply network impedance and the cross-sectional area and
length of the supply cable. Obey the local regulations. See hardware manual for guidelines in selecting between aR and gG
fuses, and for additional fuse alternatives
3) The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 and CSA C22.2 No. 274
certifications. Refer to note 6 for circuit breaker protection.
4) IEC 61439-1: The drive is suitable for use on a circuit capable of delivering not more than 65 kA when protected by the
fuses given in this table.
5) UL 61800-5-1, CSA C22.2 No. 274: The drive is suitable for use on a circuit capable of delivering not more than 100 kA
symmetrical amperes (rms) at 480 V maximum when protected by the ABB recommended fuses.
Alternate Fuses, MMPs and Circuit Breakers for ABB Drives
6) Refer to
and circuit breakers that can be used as branch circuit protection.
7) Class J, CC, and CF fuses are also allowed at the same nominal current and voltage ratings.
8) These losses are not calculated according to IEC 61800-9-2.
9) IEC Installations: The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C, PV insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-52/
2001). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
10) NEC Installations: The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly
buried). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
Input
ACQ580
rating
-31-...
Frame
IEC
size
ratings
I
1
A
U
= 3-phase 400 V
n
09A5-4
R3
8
12A7-4
R3
10
018A-4
R3
14
026A-4
R3
20
033A-4
R6
27
039A-4
R6
33
046A-4
R6
40
062A-4
R6
51
073A-4*
R6
63
088A-4*
R6
76
106A-4
R8
94
145A-4
R8
128
169A-4
R8
154
206A-4
R8
188
Input
ACQ580
rating
-31-...
Frame
IEC
size
ratings
I
1
A
U
= 3-phase 480 V
n
09A5-4
R3
7.0
12A7-4
R3
9.0
018A-4
R3
12.0
026A-4
R3
17.0
033A-4
R6
24
039A-4
R6
29
046A-4
R6
34
062A-4
R6
44
073A-4*
R6
54
088A-4*
R6
66
106A-4
R8
82
145A-4
R8
111
169A-4
R8
134
206A-4
R8
163
.
Motor
Output ratings
1)
power
I
I
P
2
Ld
Ld
A
A
kW
9.4
8.9
4.0
12.6
12.0
5.5
17.0
16.2
7.5
25
23.8
11
32
30
15
38
36
18.5
45
43
22
62
59
30
73
69
37
88
84
45
106
101
55
145
138
75
169
161
90
206
196
110
Motor
Output ratings
1)
power
I
I
P
2
Ld
Ld
A
A
kW
7.6
7.6
4.0
12.0
12.0
5.5
14.0
14.0
7.5
23.0
23.0
11
27
27
15
34
34
18.5
44
44
22
52
52
30
65
65
37
77
77
45
96
96
55
124
124
75
156
156
90
180
180
110
(3AXD50000645015
3)
Fuses
4)
2)4)
gG fuse
aR fuse
43620)
(DIN 43620)
ABB type
Bussmann type
OFAF000H16
170M1561
OFAF000H16
170M1561
OFAF000H25
170M1563
OFAF000H32
170M1563
OFAF000H40
170M1565
OFAF000H50
170M1565
OFAF000H63
170M1566
OFAF000H80
170M1567
OFAF000H100
170M1568
OFAF000H100
170M1568
-
170M1569
-
170M3817
-
170M5808
-
170M5809
3)
Fuses
4)
gG fuse
aR fuse
(DIN 43620)
(DIN 43620)
Bussmann
ABB type
type
OFAF000H16
170M1561
OFAF000H16
170M1561
OFAF000H25
170M1563
OFAF000H32
170M1563
OFAF000H40
170M1565
OFAF000H50
170M1565
OFAF000H63
170M1566
OFAF000H80
170M1567
OFAF000H100
170M1568
OFAF000H100
170M1568
-
170M1569
-
170M3817
-
170M5808
-
170M5809
[English]) for additional UL fuses
Typical power
Typical
9)
cable
power
(DIN
loss
Copper
2
mm
3x2,5+2,5
226
3x2,5+2,5
329
3x2,5+2,5
395
3x6+6
579
3x10+10
625
3x10+10
751
3x16+16
912
3x25+16
1088
3x35+16
1502
3x50+25
1904
3x70+35
1877
3x95+50
2963
3x120+70
3168
3x150+70
3990
Typical power
Typical
9)
cable
power loss
2)4)
Copper
2
mm
W
3x2.5+2.5
219
3x2.5+2.5
278
3x2.5+2.5
321
3x6+6
473
3x10+10
625
3x10+10
711
3x16+16
807
3x25+16
960
3x35+16
1223
3x50+25
1560
3x70+35
1678
3x95+50
2237
3x120+70
2796
3x150+70
3356
12
8)
W
8)