Atkinson Electronics GSCM Istruzioni per l'uso e l'installazione - Pagina 8

Sfoglia online o scarica il pdf Istruzioni per l'uso e l'installazione per Unità di controllo Atkinson Electronics GSCM. Atkinson Electronics GSCM 16. Generator start control module
Anche per Atkinson Electronics GSCM: Manuale (16 pagine)

Atkinson Electronics GSCM Istruzioni per l'uso e l'installazione
GENERATOR START CONTROL MODULE
GSCM ADJUSTMENT CHART (0 TO 5V POTENTIOMETERS)
Adjustment Formulas
0 - 60 (SEC/MIN/VBAT)
0 - 120 (SEC)
15 - 75 (Hz)
Setting the following adjustments to 0 Volts or 5 Volts on the test point causes the GSCM to operate as follows:
Adjustment
0 - 60 Second Crank Delay
Max. Crank Time
Load Transfer Delay
Load Pre-Off Delay
Battery Charge Cut-In
Battery Charge Cut-Out
Under Speed Shutdown
Over Speed Shutdown
Run/Crank Disconnect
30 Day Exercise Runtime
* Both battery cut-in and cut-out must be at maximum for switched auto start.
** Both Over Hz and Under Hz must be set at zero to disable the Over or Under Hz Shutdown.
ATKINSON ELECTRONICS, INC.
Web Site: www.atkinsonelectronics.com
TPV = (Desired Value ÷ 60) x 5
TPV = (Desired Sec ÷ 120) x 5
TPV = [(Desired Hz - 15) ÷ 60] x 5
0 Volts
5 Second Minimum
Will Not Energize Starter
Ignition and Load Relays Energize Together
Ignition and Load Relays De-energize Together
Ignores Automatic Battery Charge Function
Ignores Automatic Battery Charge Function
Ignores Under Speed Shutdown Condition**
Ignores Over Speed Shutdown Condition**
Uses 15Hz to Disconnect Starter
Deactivates 30 Day Exercise
Distributed by:
Example:
11.5V BAT = 0.96V (TPV)
55Hz = 3.33V (TPV)
65Hz = 4.17V (TPV)
Factory Default Adjustments
Crank Delay
Maximum Crank
Load Transfer Delay
Load Pre-Off Delay
Battery Cut-In Volt
Battery Cut-Out Volt
Under Speed Shutdown
Over Speed Shutdown
Run/Crank Disconnect
30 Day Exercise Runtime @ deactivated - TPV = 0
5 Volts
60 Seconds
60 Seconds
60 Seconds
120 Seconds
Switched Auto Start*
Switched Auto Start*
75Hz Under Speed Shutdown
75Hz Over Speed Shutdown
Over 60 Hz Starter Won't Disconnect
1 Hour 30 Day Run Tim
GSCM
SECTION - 8
@ 5s
- TPV = 0.42V
@ 15s
- TPV = 1.25V
@ 60s
- TPV = 5V
@ 90s
- TPV = 3.75V
@ 11.5V
- TPV = 0.96V
@ 13.5V
- TPV = 1.13V
@ 55Hz
- TPV = 3.33V
@ 65Hz
- TPV = 4.17V
@ 30Hz
- TPV = 1.25V
REV 8/06