DESCRIPTION
The fan is a continuously running extract fan for kitchens, utility rooms, bathrooms and
toilets. The electrical supply to this fan is 12V DC SELV from the mains controller. This
means that the fan may be installed within reach of a person using a fixed bath or
shower, i.e. in a nearby wall. However, for reliable operation, the fan must not be
placed where it could be submerged in water or regularly exposed to direct water
spray, e.g. from a shower head whether permanently fixed or movable.
The product incorporates an airflow detection system that detects the installation duct
resistance and maintains the correct fan speed to achieve the preset extract flow rate
(model dependant).
The incorporated LED display allows the installer to configure the fan to suit its
installation. The display is also used to show the day logger and power run meter.
The fan can be wall, window or panel mounted.
ACCESSORIES
WALL KIT stock ref. – ESG100WALL
WINDOW KIT stock ref. - AWK100
PANEL KIT stock ref. - ACKS100
150mm CONVERSION KIT stock ref. - ACR-CK46
INSTALLATION
SITING THE CONTROLLER
1.
The controller must not be installed in a shower cubicle or enclosure. It must be sited
away from direct sources of water spray and out of reach (1.5m) of a person using a
fixed bath or shower.
2.
Site away from direct sources of heat. Ambient temperature range 0 to 40ºC. Do not
site in an area containing excessive levels of grease.
3.
Decide where to site the controller and fan and work out the required cable runs.

PANEL MOUNTING

1.
Cut a 105mm diameter hole.
2.
Remove the front panel by carefully pulling
away from the fan.
3.
Loosen the two self-retaining screws and
remove the inner grille by carefully pulling
away from the housing.
4.
Using the built in spirit level bubble as an
aid. Mark the screw centres through the
holes in the fan back plate. Drill, plug and
screw into position. Attach ducting as
required for the installation.
5.
Wire the fan as described in Wiring
Section. Adjust any settings as required (see
Setup Section).
6.
After installation, ensure impeller rotates freely.
7.
Replace the inner grille and tighten the retaining screws. Replace the front panel.
Open up the internal cover to access
The spirit level bubble