Auber Instruments JSL-64A Manuale di istruzioni - Pagina 3

Sfoglia online o scarica il pdf Manuale di istruzioni per Timer Auber Instruments JSL-64A. Auber Instruments JSL-64A 5. 1/32 din general purpose timer

Auber Instruments JSL-64A Manuale di istruzioni
AUBER INSTRUMENTS
6. Parameter Settings
All parameters are listed in the table below.
Press and hold SET key for 3 seconds to enter the menu mode. For each
parameter setting, use UP or DOWN key to select different programming
values. Press SET key to confirm then exit. Please check figure 3 for details.
For the definition of each programming value, see Table 1.
Table 1. Parameter Description.
Code
Description
(Short-press SET key)
T1
Set value for T1
T1
T2
Set value for T2
T2
(Long-press SET key for 3 seconds)
Timer function, operating
FUNC
Func
mode
T1U
T1u
T1 timer unit
T2U
T2u
T2 timer unit
TDIR
Tdir
Timer counting direction
OUT
Relay output mode
Out
RUN
run
Timer triggering action
Relay action when STP
STOP
stop
key is pressed
Relay action when PAU
PAUS
paus
key is pressed
* Please note that ESP function is a new feature added to JSL-64A. It is not available in
JSL-64.
** Please note that STOP parameter will only appear in the menu when FUNC = SDL
and OUT = ONDL.
Details about each parameter
Note 1. T1 is the set value in Single Delay (SDL) mode. It is also the first set
value in in Delayed Interval Mode (DINT) and the Cycled Mode (CYCL) mode.
Note 2. T2 is the second set value in Delayed Interval Mode (DINT) or in the
Cycled Mode (CYCL). This parameter will only be displayed if the Timer Mode
FUNC is set to either DINT or CYCL mode.
Note 3: FUNC is the timer operating mode, it can be set to SDL, DINT, CYCL,
or EST.
SDL (Single Delay): The timer counts a single period of time that is
defined in T1. The relay can either be turned on during this period of timer or it
can be turned on at the end of this period of time, depends on the OUT setting.
When OUT = OFDL, the relay turns on at the beginning when timer starts
counting, and turns off when the counting stops. When OUT = ONDL, the relay
2021.03
Range
Initial
Set Values
1:10
1.10
Parameters
SDL,
DINT,
sdl
CYCL,
EST *
S,
M:S
M:S,
M,
S
H:M
UP, DN
DN
OFDL,
OFDL
ONDL
RST, PU
RST
0, 1
0
0, 1
1
stays off when timer starts counting, and the relay turns on when the timer
reaches the set value till the RST (reset) key is pressed or when the power to
the device is cycled. Please refer to Note 6 for details about OUT parameter.
In Single Delay and On-Delay mode (i.e., FUNC = SDL, OUT = ONDL), a
special parameter "STOP" will appear in the parameter menu. For details
please refer to the Note 8 below.
DINT (Delayed Interval): The timer will count time for two periods of time,
No
T1 and T2, and then stops. Relay action depends on the OUT setting. When
te
OUT =OFDL, the relay turns on at the end of T1, stays on during T2 time, and
then turns off at the end of T2 time. When OUT = ONDL, the relay turns on at
the beginning at T1 time, turns off at the end of T1 time, stays off during T2,
1
and then turns on again at the end of T2 time. This is a single action process.
2
CYCL (Cycle): The timer will repeat a counting cycle that consists of two
periods of time, T1 and T2. The relay turns on/off during each cycle depending
on the OUT setting. When OUT = OFDL, the relay turns on at the end of T1,
stays on during T2 time, and then turns off at the end of T2 time. When OUT =
3 *
ONDL, the relay turns on at the beginning at T1 time, turns off at the end of T1
time, stays off during T2, and then turns on again at the end of T2 time. This
cycle will be immediately repeated till it is stopped or reset.
4
EST (Espresso Shot Timer): This is a special mode designed for counting
the shot time (brew time) on an espresso machine. The timer display resets to
5
zero and it starts counting up when the pin 9 and 10 are shorted together. The
timer stops counting when terminal 9 and 10 are disconnected. The time unit is
6
determined by the parameter T1U. Pressing the RST key can clear the display.
7
The relay output, STP key, and PAU key are not functional in this mode. The
settings of parameter T2U, TDIR, OUT, RUN, STOP, and PAUS are irrelevant
8 **
to this mode.
9
Note 4. T1U and T2U define the time unit for T1 and T2. (Note, T2 is only
available when FUNC = DINT or CYCL).
Settings
S
M:S
M
H:M
Note 5. TDIR determines the Timer Counting Direction.
UP: counting up.
DN: counting down.
Note 6. OUT determines the relay output status as the timer runs.
OFDL (off-delay): the relay will turn ON when timer starts counting and
the relay will turn OFF when the timer reaches the set value.
ONDL (on-delay): the relay will stay OFF when the timer starts counting
and the relay will turn ON when the timer reaches the set value.
Note 7. RUN determines how does the timer start counting.
PU (power up): the timer starts counting when the device is powered up.
RST (reset): the timer starts when reset button is pressed and released.
WWW.AUBERINS.COM
Description
Range
Seconds
0.01 s ~ 99.99 s
Minutes: Seconds
1 s ~ 99 m 59 s
Minutes
1 m ~ 9999 m
Hours: Minutes
1 m ~ 99 h 59 m
P3/5