Anywire ASLINKER BL2LN87SB-02DS-CC20 Manuale del prodotto del sistema - Pagina 10

Sfoglia online o scarica il pdf Manuale del prodotto del sistema per Adattatore Anywire ASLINKER BL2LN87SB-02DS-CC20. Anywire ASLINKER BL2LN87SB-02DS-CC20 20.

Address setting
An address number is set as a beginning number from which part of the transmission frame is occupied to the terminal.
Set the address number within the range of bit address "0 to 254."
- Set the address number so that the area occupied by the terminal does not exceed the transmission points of the master unit.
- Make sure that the address number setting is not duplicated.
- Also, use the address writer to read an address number that has been written in the terminal.
The factory-set address is "bit address 255" or "bit address 511," which indicates that an address
CAUTION
has not been set.
The factory-set address varies depending on lot No., as follows:
Input and output operations are disabled with the factory-set
address.
Parameter setting
■Disconnection monitoring function setting
This parameter is used to specify whether the disconnection detecting function is enabled or disabled, and the target
for monitoring.
Variable
0
1
2
Monitoring enabled for both power supply and signal lines
3
Although the unit can be used with the setting of "monitor both power supply and signal lines" with the
CAUTION
connection of 2-wire type sensors, I/O disconnection may be caused depending on the sensor to be connected.
If that happens, change the setting as follows.
Example 1: "Signal line disconnection" occurs all the time. → Set to "Monitoring enabled for power supply
Example 2: "Power supply line disconnection" occurs all the time. → Set to "Monitoring enabled for signal
Example 3: Both "power supply line disconnection" and "signal line disconnection" occur. → Turn OFF the
*
■Disconnection detection enabled CH setting
This parameter is used to specify channels supporting the disconnection detecting function.
Variable
0
1
2
■Short-circuit noti cation cancel setting
This parameter is used to specify how to clear short-circuit status after short-circuit is detected.
Variable
Automatic restoration
0
Manual restoration
1
For S/W version "B" or later version: Bit address 511
For S/W version "A" or 3-digit lot No.: Bit address 255
Description
Disconnection detecting function OFF
Monitoring enabled for power supply line only
Monitoring enabled for signal line only
line only."
line only."
disconnection detecting function (disconnection detection disabled).
It is not possible to change the setting channel by channel. Pay attention to the setting if both 2-wire and
3-wire type sensors are used.
Description
Both IN0 and IN1
IN0 only
IN1 only
[Equipment parameter 12]
Description
-BL2LN87SB02D*CC20 10/20-
[Equipment parameter 1]
[Equipment parameter 2]
Factory setting: 0
Factory setting: 0
Example:
Lot No. 19ECBNB
S/W version
Factory setting: 3