The devices return an analogue value depending on their state. The table below shows these values and their
definitions
AV
Definition
0
Battery pack A and B missing
1
Detector fault, sounder audio fault
2
Head missing
3
Sounder missing
4
Tamper
5
Signal strength fault, background RSSI out of range - Interface
6
Not used
7
Battery fault 30 days, A and B
8-12
Not used
13
Signal strength poor
14
Signal strength low
15
Not used
16
Normal - MCP, sounder, loop interface, I/O unit
17-19
Not used
20
Signal strength medium - detector
21-24
Not used
25
Signal strength good - detector
26-34
Not used - detector
35
Head dirty detector
36-49
Not Used
50
Pre-alarm - detector
51-63
Not used
64
Alarm - MCP
65-84
Not used
85
Alarm - detector
Note: No response to polling indicates an RF comm failure
Appendix B
Multiple interfaces - channel selection
XPander
Interfaces on
Site
1
2
3
4
5
Q.1
Q.2
Q.3
Q.4
Q.5
Please complete on commissioning
1st Channel Selected
Ch 08
Ch 16
Ch 01
Ch 04
Ch 12
If there is more than one XPander Interface on the site: have ALL
the channels been set as above?
Has the XPander Interface been installed as per the survey and
installation instructions, allowing two metres from electrical
equipment and other XPander Interfaces?
Has the aerial been installed as per the survey and installation
instructions, allowing 400mm from any metal object or other
equipment?
Are ALL the device signal levels 50% or above?
Has the XPander site survey sheet been fully completed?
© Apollo Fire Detectors Limited 2015
2nd Channel Selected
Ch 26
Ch 32
Ch 20
Ch 23
Ch 29
14