AC MGA0800/A1 Manuale d'uso - Pagina 15

Sfoglia online o scarica il pdf Manuale d'uso per Condizionatore d'aria AC MGA0800/A1. AC MGA0800/A1 16.

External fan can't
run
Fan makes
abnormal noise
Heater can't run
Maintenance
8
Maintaining air conditioner very closely can keep it having a good performance and normal life, the
following works should be done:
No.
1
Check whether there are alarm information or not
2
Check whether fans can rotate normally or not
3
Check whether compressor can rotate normally or not
4
Check whether there is obvious noise or shake or not
Clean the inner and outer circulation air inlet and outlet of the air
5
conditioner
6
Clean heat exchangers
Check whether air conditioner power supply wire and communication wire
7
is Ok or not
External fan is fault
The operating condition has not
been satisfied
External fan line has not been
connected correctly
External fan is stuck
Fan blades are damaged or the
bearing of fan wears
The blades of fan scratch other
objects
The heater is fault
The heater lines has not been
connected correctly
The operating condition has not
been satisfied
Check/Maintain
Change the external fan
Check if the operating condition is satisfied
Check the external fan line,and connect it again
Check if there are block to stick the fan, and clear
the block
Change the damaged fan
Check and fix it again
Change the heater
Check the external fan line,and connect it again
Check if the operating condition is satisfied
14
Cycle
6 months
6 months
6 months
6 months
6 months
1year
1year