ADEMCO 5808LSTA Istruzioni per l'installazione - Pagina 2

Sfoglia online o scarica il pdf Istruzioni per l'installazione per Allarme fumo ADEMCO 5808LSTA. ADEMCO 5808LSTA 4. Photoelectronic smoke/heat detector with built-in wireless transmitter

ADEMCO 5808LSTA Istruzioni per l'installazione
5808LSTA Photoelectronic Smoke/Heat Detector with
Built-in Wireless Transmitter Installation Instructions
SPECIFICATIONS
Power Source:
Height:
Diameter:
Weight:
Operating Ambient Temperature Range: 0° to 38° C (32° to 100° F)
Operating Humidity Range:
Heat Sensor:
Low Temperature Sensor
Agency Listings:
Before installing detectors, please thoroughly read these installation
instructions and Manual I56-407, Guide for Proper Use of System Smoke
Detectors, which provides detailed information on detector spacing, place-
ment, zoning, wiring, and special applications. Copies of this manual are
available from ADEMCO.
NOTICE: This manual should be left with the owner/user of this equip-
ment.
IMPORTANT: This detector must be tested and maintained regularly fol-
lowing CAN/ULC S536 requirements. The detector should be cleaned at
least once a year.

GENERAL DESCRIPTION

The 5808LSTA photoelectronic smoke/heat detector with built-in wireless
transmitter is intended for use with wireless alarm systems that support
5800 series devices. Refer to control/communicator installation instructions
for compatibility. The 5808LSTA smoke/heat detector can be used with
5881 series (L, M, H) and 5881EH receivers for residential installations.
For commercial installations, the 5881EH receiver should be used. The
transmitter can send alarm, tamper, maintenance (when control panels
are equipped to process maintenance signals), and battery condition mes-
sages to the system's receiver. The maintenance signal fully complies
with the sensitivity test requirement specified in NFPA 72, 7-2.2. Refer to
the wireless system's instructions for the maximum number of transmitters
that can be supported.
The 5808LSTA will sound its built-in temporal horn when smoke acti-
vates the detector (also the LED also flashes rapidly), or when the air
temperature reaches 135° F (the LED flashes normally, about once every
40 seconds). A message is also sent to the wireless control panel and the
smoke detector's ID number is displayed at the console. The alarm mes-
sage is transmitted every 4 seconds until the smoke condition has cleared
and the detector has reset. After the horn stops, a RESTORE message is
transmitted to the control panel and the ID number can be cleared from
the panel. During normal and low battery conditions, the LED flashes
approximately once every 40 seconds. The built-in Drift Compensation
algorithm automatically maintains the sensitivity of the detector. Once the
detector reaches its limit of compensation, it transmits a maintenance
signal to the panel. In maintenance condition, the LED stops flashing.
BATTERY INSTALLATION AND REPLACEMENT
The 5808LSTA is powered by two 3-volt CR123A or DL123A Lithium bat-
teries (included). The detector checks for low batteries at least every 60
minutes. If a low battery is detected, the transmitter sends a low battery
message to the control panel, which beeps and displays the detector's
ID. Unit will send low battery signal to control when it detects low battery
below 5.1V. This condition will exist for a minimum of seven days, and
then the detector's horn will "chirp" about every 40 seconds. The batteries
AD300-00-00
Two 3-volt CR123A Lithium Batteries (included). (Replace with Duracell
DL123A, Sanyo CR123A, Panasonic CR123A or ADEMCO 466.)
2.05 inches (52 mm)
5.0 inches (127 mm) without adapter bracket
5.5 inches (140 mm) with adapter bracket
8.5 oz. (241 g) without batteries
5% to 95% Relative Humidity
57°C (135° F) Fixed Temperature Electronic Thermistors
7°C ± 3°C (44.6°F ± 5.4°F) for 3.5 ± 0.5 hrs
ULC, UL 268 – Commercial and Residential Installations
should be replaced BEFORE the chirps begin. BE SURE TO REPLACE
BOTH BATTERIES WITH FRESH ONES.
To replace batteries:
1. Remove the detector from its mounting plate by twisting the detector
counterclockwise. Remove batteries, and dispose properly.
2. Install two new 3-volt CR123A Lithium batteries in the battery com-
partment. Follow the polarity diagram inside the compartment.
3. Reinstall the smoke detector onto the mounting plate by turning the
detector clockwise.
4. Test the detector as described in the TESTING TRANSMITTER
SIGNAL section of this manual. The LED should flash about once
every 40 seconds to indicate normal operation. If the batteries are not
installed correctly, the smoke detector will not operate and the batter-
ies may be damaged. If the detector does not appear to be sending a
signal during any of the tests, check for correct battery installation.
Indicator Light
Pulsing: Normal/Thermal Alarm
Fast Blink: Smoke Alarm
None: Call for Service
Figure 1. 5808LSTA Wireless Smoke/ Heat Detector
PROGRAMMING
The smoke detector's ID must be enrolled in the control panel during
installation of the system. The 5808LST must be enrolled on loop 1 as an
input "Type 3" (supervised RF).
Both heat and smoke detection transmit as Loop 1. Maintenance signal
is transmitted as Loop 2, Low temperature is transmitted as Loop 3 and
tamper is transmitted as Loop 4. To take advantage of these value added
features, these loops can be assigned to individual zones on the 5800
series wireless compatible panel.
1
Test Switch
A78-2332-03
I56-2249-00
ADEMCO, Woodbridge, Ontario.