Afriso EURO-INDEX ARM Manuale - Pagina 2

Sfoglia online o scarica il pdf Manuale per Controllore Afriso EURO-INDEX ARM. Afriso EURO-INDEX ARM 2. Electrical actuator

Afriso EURO-INDEX ARM Manuale
Setting the auxiliary switch (selected versions)
Procedure for setting the auxiliary switch:
1.
Loosen two fixing screws "i" and
remove the actuator housing
(fig.
1).
2.
Carefully remove the switching ring
(fig.
5). The thicker ring section which
moves below the switch while the
actuator operates, applies pressure to
the lever and thus opens of contacts
4-5 of the auxiliary switch.The function
of the auxiliary switch (closing of
contacts 4-5) is initiated when the
thinner ring section faces the switch
which triggers the lever. At the same
time, the signal lamp lights up.
Operation of the actuator
1. Operating mode of the actuator
The operating mode is set by means of
the selector for manual mode "j"
(fig.
Operating mode Automatic: The actuator
is in operating mode Automatic when the
selector "j" is in position
.
Operating mode Manual: The actuator is in
operating mode Manual when the selector
"j" is in position
.
2. Indication via signal LEDs
Three signal LEDs are integrated into the
housing of the actuator. The outer LEDs
indicate the direction of rotation of the
Maintenance
The AFRISO ARM actuator is maintenance-free.
Figure 3
Figure 5
instrukcja prosta do pudelka.indd 2
3.
After the actuator has been set to position
"5" of the adjustment scale at the adjustment
handle (50 % open) and the valve opening
direction has been determined, set the angle
of the actuator (range 0 - 90°) at which the
function of the auxiliary switch is to be
triggered.
4.
Carefully push in the ring in such a way that
the end of the thicker section of the
circumference coincides with the specified
switch triggering angle.
5.
Refit the upper part of the actuator housing
and tighten the fixing screws "i".
actuator. The centre LED indicates the
operating state of the auxiliary switch
(depending on the version of the actuator).
1).
3. Position of adjustment handle with
adjustment scale
After the actuator has been mounted to the
mixing valve and the proper adjustment
scale selected, position "0" means that the
valve is fully closed (hot water supply
closed) and position "10" means that the
valve is fully opened (hot water supply
open). The other settings of the adjustment
scale represent the degree of opening
(for example, "4" means that the valve is
open by 40%).
orange
(direction of rotation left)
red
(auxiliary switch active)
orange
(direction of rotation right)
Technical specifications
Parameter
Torque
Rotation angle
Time for turn by 90°
Supply voltage / control signal
Operating temperature range
Power input
Power consumption
Protection class
Degree of protection
Dimensions (H x W x D):
Weight
Housing material
Approvals and certificates
The electrical actuator ARM complies with the Low Voltage Directive (LVD) (2006/95/EC),
Electromagnetic Compatibility Directive (EMC) (2004/108/EC) and Restriction
of Hazardous Substances Directive (RoHS) (2002/95/EC)
The electrical actuator ARM also complies with the following standards:
EN 60730-1, EN60730-2-14.
Taking out of service, disposal
1.
Disconnect the device from the
supply voltage.
2. Dismount the device.
3. To protect the environment, this
device must not be disposed of
together with non-separated
Warranty
The warranty of the manufacturer for this
product is 36 months after the date of
purchase. The warranty shall be void if
unauthorised modifications are made to the
product or if the product is not installed in
compliance with these instructions.
5
6
Page
7
8
Figure 4
3-point
N L
230 V (24 V) ~
1
2
3
N
2-point
N L
230 V (24 V) ~
1
2
3
N L
proportional
~
AC 24 V
+ -
DC 24 V
Y DC 0(2)...10 V
0(4)...20 mA
U DC 0(2)...10 V
1 2 3
4
~
Y U
-
+
Value
Depending on version: 6 Nm, 10 Nm, 15 Nm
90°
Depending on version:
15 s, 30 s, 60 s, 120 s, 240 s, 480 s
2-point - 24 V AC / 230 V AC
3-point - 24 V AC / 230 V AC
proportional - 24 V AC/DC
(0..10 V, 2..10 V, 0..20 mA, 4..20 mA)
Setting in range 0 ÷ 90° (250 V AC, 3 A)
0 ÷ 50°C
2,5 ÷ 4 VA
II
IP42
84 × 102 × 90 mm
Version 6 Nm: 390 g ÷ 630 g
Version 10 Nm and 15 Nm: 600 g ÷ 860 g
PC
commercial waste. Take the device to
an official waste disposal company.
The electrical actuator ARM consists of
recyclable materials.
Customer satisfaction
Customer satisfaction is the prime objective of
AFRISO-EURO-INDEX. Please contact us at
[email protected] if you have any questions,
suggestions or problems concerning product.
3-point + auxiliary switch
N L
230 V (24 V) ~
4
1 2 3
4
5
6
N
3-point + auxiliary switch
N L
230 V (24 V) ~
1 2 3
4
4
5
6
N
L
Signal
S1
S2
S3
0
0
U
0
0...10 V / 0...20 mA
1
1
I
1
2...10 V / 4...20 mA
S4
S5
S6
0
0
0
60s
1
0
1
90s
1
0
120s
1
1
120s
0
1
1
0
U/I
11-04-05 10:50