Sfoglia online o scarica il pdf Manuale di installazione e avviamento rapido per Apparecchiature industriali ABB ACQ580-31 Series. ABB ACQ580-31 Series 16. Converter modules with electrolytic dc capacitors in the dc link
Anche per ABB ACQ580-31 Series: Manuale (16 pagine)
R6
2 N·m
L1, L2, L3, T1/U, T2/V, T3/W: 5.6 N·m (4.1 lbf·ft)
R8
2 N·m
L1, L2, L3: 30 N·m (22.0 lbf·ft)
T1/U, T2/V, T3/W: 30 N·m (22.0 lbf·ft)
5.
Frame R8: Install the side plates if removed in step 2. Attach the cables outside the drive mechanically.
6.
Install the shroud onto the power cable connection terminals.
R6
7.
Ground the motor cable shield at the motor end. For minimum radio frequency interference, ground the motor cable
shield 360 degrees at the cable entry of the motor terminal box.
2.9 N·m
(2.1 lbf·ft)
4a
9.8 N·m
(7.2 lbf·ft)
4a
4c
4b
4c
4b
R8
6
2.9 N·m
9.8 N·m