ABB ACS880-01 Series Manuale di installazione rapida - Pagina 12

Sfoglia online o scarica il pdf Manuale di installazione rapida per Apparecchiature industriali ABB ACS880-01 Series. ABB ACS880-01 Series 14. Industrial drives
Anche per ABB ACS880-01 Series: Manuale di installazione (20 pagine), Manuale (16 pagine), Manuale di installazione e avviamento rapido (17 pagine), Manuale d'uso (18 pagine)

ABB ACS880-01 Series Manuale di installazione rapida
12 EN – Quick installation guide
Wire sizes:
2
0.5 ... 2.5 mm
(24...12 AWG)
Tightening
torques: 0.5 N·m
(5 lbf·in) for both
stranded and
solid wiring.
EN
DA
DE
ES
FI
FR
IT
1)
Total load
capacity of these
NL
outputs is 4.8 W
(200 mA / 24 V)
PT
minus the power
taken by the option
modules installed
RU
on the board.
SV
TR
CN
XPOW External power input
1
2
XAI
Reference voltage and analog inputs
1
2
3
4
5
6
7
J1
J2
XAO
Analog outputs
1
2
3
4
XD2D
Drive-to-drive link
1
2
3
J3
XRO1, XRO2, XRO3 Relay outputs
1
2
3
1
2
3
Fault
1
2
3
XD24
Digital interlock
1
2
3
4
5
DIOGND Digital input/output ground
J6
Ground selection switch
XDIO
Digital input/outputs
1
2
XDI
Digital inputs
1
2
3
4
5
6
XSTO
Safe torque off
1
2
3
4
X12
Safety functions module connection
X13
Control panel connection
X205
Memory unit connection
+24VI
24 V DC, 2 A
GND
+VREF
10 V DC, R
1...10 kohm
L
-VREF
-10 V DC, R
1...10 kohm
L
AGND
Ground
AI1+
Speed reference 0(2)...10 V, R
200 kohm
AI1-
AI2+
By default not in use. 0(4)...20 mA, R
100 ohm
AI2-
J1
AI1 current/voltage selection jumper
J2
AI2 current/voltage selection jumper
AO1
Motor speed rpm 0...20 mA, R
500 ohm
AGND
AO2
Motor current 0...20 mA, R
AGND
B
A
Drive-to-drive link
BGND
J3
Drive-to-drive link termination switch
NC
Ready
250 V AC / 30 V DC
COM
2 A
NO
NC
Running
250 V AC / 30 V DC
COM
2 A
NO
NC
Faulted(-1)
COM
250 V AC / 30 V DC
2 A
NO
DIIL
By default not in use.
+24VD
+24 V DC 200 mA
DICOM
Digital input ground
+24VD
+24 V DC 200 mA
DIO1
Output: Ready
DIO2
Output: Running
DI1
Stop (0) / Start (1)
DI2
Forward (0) / Reverse (1)
DI3
Reset
DI4
Acceleration & deceleration select
DI5
Constant speed select
DI6
By default not in use.
OUT1
SGND
Safe torque off. Both circuits must be
closed for the drive to start.
IN1
IN2
>
in
>
in
<
L
< 500 ohm
L
1)
1)