Warnings and faults

Warning Fault
Aux. code
A2A1
2281
Current calibration
A2B1
2310
Overcurrent
A2B3
2330
Earth leakage
A2B4
2340
Short circuit
-
3130
Input phase loss
-
3181
Wiring or earth fault
A3A1
3210
DC link overvoltage
A3A2
3220
DC link undervoltage
-
3381
Output phase loss
-
5090
STO hardware failure
A5A0
5091
Safe torque off
A7CE
6681
EFB comm loss
A7C1
7510
FBA A communication
A7AB
-
Extension I/O
configuration failure
AFF6
-
Identification run
-
FA81
Safe torque off 1
-
FA82
Safe torque off 2
Ratings, fuses and typical power cable sizes
ACQ580-
Nominal ratings
01-...
Input
Output
current
current
light duty
I
I
1
LD
A
A
U
= 200...240 V, P
at U
= 3-phase 208/230 V, 60 Hz
1
n
n
04A6-2
4.6
4.6
06A6-2
6.6
6.6
07A5-2
7.5
7.5
10A6-2
10.6
10.6
017A-2
16.7
16.7
024A-2
24.2
24.2
031A-2
30.8
30.8
046A-2
46.2
46.2
059A-2
59.4
59.4
U
= 440...480 V, P
at U
= 3-phase 460 V, 60 Hz
1
n
n
02A1-4
2.1
2.1
03A0-4
3.0
3.0
03A5-4
3.5
3.5
04A8-4
4.8
4.8
06A0-4
6.0
6.0
07A6-4
7.6
7.6
012A-4
12.0
12.0
014A-4
14.0
14.0
023A-4
23.0
23.0
027A-4
27.0
27.0
034A-4
34.0
34.0
044A-4
44.0
44.0
U
= 500...600 V, P
at U
= 3-phase 575 V, 60 Hz
1
n
n
Description
Warning: Current calibration is done at the next start.
Fault: Output phase current measurement fault.
The output current is more than the internal limit. This can also be caused by
an earth fault or phase loss.
A load unbalance that is typically caused by an earth fault in the motor or the
motor cable.
There is a short-circuit in the motor or the motor cable.
The intermediate DC circuit voltage oscillates due to missing input power
line phase.
Incorrect input and motor cable connection.
Intermediate DC circuit voltage is too high.
Intermediate DC circuit voltage is too low.
All three phases are not connected to the motor.
STO hardware diagnostics has detected hardware failure. Contact ABB.
The Safe torque off (STO) function is active.
Break in embedded fieldbus communication.
Communication lost between drive (or PLC) and fieldbus adapter.
The installed C-type module is not the same as configured, or there is an
error in the communication between the drive and module.
The motor ID run occurs at the next start.
The Safe torque off circuit 1 is broken.
The Safe torque off circuit 2 is broken.
4)
Fuses
Motor
gG fuse
1)
2)
power
(IEC 60269)
P
P
ABB type
n
LD
kW
hp
0.75
1.0
OFAF000H25
1.1
1.5
OFAF000H25
1.5
2.0
OFAF000H25
3.0
3.0
OFAF000H25
4.0
5.0
OFAF000H25
5.5
7.5
OFAF000H40
7.5
10.0
OFAF000H40
11.0
15.0
OFAF000H63
15
20
OFAF000H63
0.75
1.0
OFAF000H4
1.1
1.5
OFAF000H6
1.5
2.0
OFAF000H6
2.2
3.0
OFAF000H10
3.0
3.0
OFAF000H10
4.0
5.0
OFAF000H16
5.5
7.5
OFAF000H16
7.5
10.0
OFAF000H25
11.0
15.0
OFAF000H32
15.0
20.0
OFAF000H40
18.5
25.0
OFAF000H50
22.0
30.0
OFAF000H63
Typical power cable sizes,
Cu
uR/aR
UL class
3)5)
6)7)8)
fuse
T
(DIN 43620)
Bussmann type
mm
170M1563
JJS-15
3×1.5 + 1.5
170M1563
JJS-15
3×1.5 + 1.5
170M1563
JJS-15
3×1.5 + 1.5
170M1563
JJS-15
3×1.5 + 1.5
170M1563
JJS-30
3×2.5 + 2.5
170M1565
JJS-40
3×4.0 + 4.0
170M1565
JJS-40
3×6.0 + 6.0
170M1566
JJS-80
3×10 + 10
170M1566
JJS-80
3×10 + 10
170M1561
JJS-15
3×1.5 + 1.5
170M1561
JJS-15
3×1.5 + 1.5
170M1561
JJS-15
3×1.5 + 1.5
170M1561
JJS-15
3×1.5 + 1.5
170M1561
JJS-15
3×1.5 + 1.5
170M1561
JJS-15
3×2.5 + 2.5
170M1561
JJS-15
3×2.5 + 2.5
170M1563
JJS-30
3×2.5 + 2.5
170M1563
JJS-30
3×6 + 6
170M1565
JJS-40
3×10 + 10
170M1565
JJS-60
3×10 + 10
170M1566
JJS-60
3×10 + 10
Frame
size
2 9)
10)
AWG
14
R1
14
R1
14
R1
14
R1
10
R1
8
R2
8
R2
6
R3
4
R3
14
R1
14
R1
14
R1
14
R1
14
R1
14
R1
14
R1
12
R2
10
R2
8
R3
8
R3
6
R3