ABB FDNA-01 Manuale di installazione e avviamento rapido
Pin allocation for [X1]
1 2 3 4 5
Pin
Description
1
V-
Network power supply
ground (0V DC)
2
CAN_L
CAN_L bus line
3
SHLD
Network cable shield
4
CAN_H
CAN_H bus line
5
V+
Network power supply
source (24V DC)
Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters.
See the appropriate drive manual.
Basic parameter settings
Index
Name
20.01
Ext1 commands
22.11
Speed ref1 source
28.11
Frequency ref1 source
50.01
FBA A enable
50.02
FBA A comm loss func
51.02
MAC ID
To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par refresh.
Further information
See the latest version of FDNA-01 DeviceNet adapter
module user's manual (3AFE68573360 [English]) in ABB
library (www.abb.com/drives/documents)
FDNA-01 manual
3AXD50000158515 Rev A (EN) 2017-11-23
Bus termination
The module does not provide bus termination. The DeviceNet
network should be terminated at both ends of the trunk cable with
a 121 ohm, ¼ W, 1% metal film resistor.
Connect the resistor between the two signal wires (CAN_H,
CAN_L) on the DeviceNet cable, as shown in this figure.
Scanner
121
1%
Metal Film
1/4 W
Value
Fieldbus A
FBA A ref 1
FBA A ref 1
Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.
Fault
Set the MAC ID number for the drive.
For more information on fieldbus options and protocols
provided by ABB Drives, see the fieldbus
communications web page
.
(new.abb.com/drives/connectivity/fieldbus-connectivity).
...
Node 1
CAN_H
CAN_L
Fieldbus communications web page
Node n
121
1%
Metal Film
1/4 W