DISCOVER 950-0023 Manuale di installazione - Pagina 4
Sfoglia online o scarica il pdf Manuale di installazione per Cremagliere e cavalletti DISCOVER 950-0023. DISCOVER 950-0023 6. Wall mount bracket for aes battery
Anche per DISCOVER 950-0023: Manuale di installazione (6 pagine)
2.2 Wall Mount Overview
Each battery requires a separate bracket. Attach the bracket to the wall before attaching the AES battery to the wall mount.
Each bracket requires a minimum of four 1/4 inch diameter lag bolts or other fasteners. Fasteners must be strong enough to
support 227 kg (500 lbs).
Mounting Surface
Wood Studs 16 inch on-center
Wood studs not 16 inch on-center
(3/4 inch min. plywood panel required)
Steel studs at 16 inch on-center (min. 18 gauge)
4.25in
18.72in
4.25in
4.25in
950-0019 AES Wall Mount
Bracket for AES 42-48-6650
4
1/4 inch Diameter x 3 1/2 inch long lag bolt
1/4 inch diameter x 1 inch long wood screw
1/4 inch diameter self-drilling screw
16in
12in
3.19in
3.19in
3.19in
3.19in
17.18in
If the wall does not have 16 inch on-center studs, adequate
support for the bracket will have to be provided. For example, a
sheet of plywood can be attached to the wall, and the bracket can
then be attached to the plywood.
Minimum Required Fastener
1.77in
950-0023 AES Wall Mount
Bracket for AES 44-48-3000
▲
NOTE
Minimum Number of
Fasteners Per Wall Mount
4
6
4
16
12
17.18
discoverbattery.com