Located on the rear of the unit is a (14) fourteen terminal connector which interfaces with the output module, provides the
115VAC input, and also provides four auxiliary outputs. A (6) six terminal connector for transducer input and a D9 connector for
RS485 communication are also located on the rear of the unit.
1.2 Output Board Features and Functions
The output board is the press/Ram-Set interface. It contains the relays used to connect to the press shut height controls.
"Up/Down Relays" - These triple pole relays should be tied into the appropriate Ram-adjust motor starter.
"In-Position Relay" - This relay will energize when the customer programmed shut height is achieved. The controller
allows programming of a +/- value at which the "in-position" relay will stay energized. The output of this relay could be
used for visual indication or as an interface to the press control alerting the user to possible slide drift.
"Run Relay" - This relay energizes when the mode select keyswitch is positioned in the "standby" mode. The relay is
usually tied into the same circuit as the existing press run-interlock switch. The objective is to let the press controls receive
positive feedback that slide adjustment is no longer possible.
The output module accepts 115VAC to operate the relays and provide an auxiliary 24VDC output. Terminals are provided for
the 115VAC power input, an auxiliary input, relay inputs from the controller, and the relay outputs.
Installation and Maintenance Manual
Chapter 1: General Description