4. The bypass damper is fully open.
5. The humidifier is mounted level on the duct.
6. There is nothing inside the duct behind the bypass collar and
damper or the humidifier body.
7. The humidifier and bypass collar and damper are level.
BAD INSTALLATION
Figure 2
SUPPLY DUCT
WARM AIR
1. The humidifier body is installed too low and will be difficult to
work on.
2. The humidifier body and bypass collar and damper are not
level. This will restrict air-flow through the humidifier as well
as create uneven air-flow over the evaporator pad and
activating sensor.
3. The bypass damper is not fully open, This will restrict air flow
through the humidifier and reduce output.
4. The humidifier is being drained to a bucket rather than a
proper drain. This will result in damage to the home.
BAD INSTALLATION
Figure 3
SUPPLY DUCT
WARM AIR
RETURN DUCT
COLD AIR
Bypass damper
not open
Unit installed
too low
Unit draining
to a bucket
RETURN DUCT
COLD AIR
Bypass collar and
humidifier not parallel
Sagging bypass tube
1. The humidifier body and bypass collar and damper are not
level. This will restrict air flow through the humidifier as well
as create uneven air-flow over the evaporator pad and
activating sensors.
2. The aluminum flex bypass tube is not cut to length and is
sagging. This will result in reduced air-flow over the evaporator
pad and will affect the performance of the activating sensors.
BAD INSTALLATION
Figure 4
SUPPLY DUCT
WARM AIR
Air conditioning
A-frame blocking
the air flow
1. The bypass collar and damper are installed in front of the
furnace's air-conditioning coils. This will not only greatly affect
the performance of the humidifier and cause malfunctions in
the activating sensors, the homeowner risked damaging the
air-conditioning coils. This would also be the case if the
humidifier were installed in front of the air-conditioning coils.
• INSTALLATION TIP: In this type of installation the
installer should mount the bypass collar and damper at
least 6" above the air-conditioning coils and use hard
metal ducting and elbows (sold separately) rather than
the flex tube. While the humidifier and bypass collar and
damper will not be level the use of hard ducting rather
than the flex ducting will make up for any restrictions or
turbulence which would occur in aluminum flex tube.
RETURN DUCT
COLD AIR