sampling was undertaken before and after an AOM EAN Series electrostatic precipitators with a face velocity of 2.5
m/s and concluded:
These results indicate that the kitchen exhaust treatment systems tested are in our opinion capable of achieving an
equivalent filtration efficiency of at least 98%. This is assuming regular maintenance is carried out to ensure the systems
are operating correctly.
6.1.5
Note: Defined testing ranges follow typical particle sizes for the exhaust emissions from kitchen exhausts as defined in
AIRAH Technical Bulletin 2016: Fire Safety Kitchen Hood Exhaust Systems:
‐
Smoke: up to 0.5 micron
‐
Grease steam: 0.5 – 6 micron
‐
Grease splatter: greater than 6 micron
6.1.6
AOM EAN Series Electrostatic Precipitators manufacture
filtration efficiency tests were carried out on an EAN 200
electrostatic precipitator based on the efficiency rate test
method US Environmental Protection Agency (EPA) / Taiwan
Environmental Protection Bureau standard. Testing was
carried out on 'Chinese cooking type' oil smoke as a testing
sample at different speeds through the filter (equivalent to a
heavy Type 4 cooking). Filtration efficiency and resistance of the
filter was determined for these different speeds as shown on the
following graph.
6.1.7
AOM EAN ESP filters are independently certified to the following:
‐
CE certified to European Directive 2004/108/EC for electromagnetic compatibility (certificate available on
request).
‐
TUVReinland tested and certified for conducted emissions and radiated emissions based on FCC Part 18.
6.1.8
Independent odour emissions testing of AOM Electrostatic filtration and Ozone injection equipment installed at a
McDonald's restaurant by a NATA‐Accredited TOU Sydney Laboratory to AS/NZS4323.3:2001 Standard found that the
AOM system had:
‐
A lower limit odour destruction efficiency of 69%
‐
An upper limit odour destruction efficiency of 86.6%
‐
A mean odour destruction efficiency of 79.6%
7
INSTALLATION GUIDELINES
7.1
General
7.1.1
Only qualified personnel should install the EAN ESP unit.
7.1.2
Personnel should have a clear understanding of these instructions and all applicable local and national building and fire
codes.
7.1.3
Personnel should be aware of general safety precautions.