- ページ 11
アクセサリー APOLON RCWC-04D11のPDF 操作マニュアルをオンラインで閲覧またはダウンロードできます。APOLON RCWC-04D11 20 ページ。 Provision store compressor condeser unit
Operation manual RCWC-04D11
If no oil level is detected on the sight glass, do not undertake running
of the compressor! Add oil of the same brand or a compatible one.
14. After the compressor is heated, the suction valves of the freezer and
cooler (V10 and V11) open
15. The liquid valves of the cooler and freezer V9 and V8 open
16.
The liquid valve of the condenser VK1 or VK2 opens,
service port remains
the water regulating valve.
17.
The switches of the cooler and freezers are turned on
18.
The compressor selected via the refrigerant valves is started from the
switch of the control panel
19.
The compressor needs to start operating and its amperemeter and
gauges shall be observed. The operating current must be less than
7.5A and the high pressure must be lower than 20 bar.
20.
The compressor shall switch off based on low pressure
21.
Valve V5 or V6 opens
22.
Valve VR2 or VR4 starts to open slowly. The compressor shall start
working. The valve shall be used to maintain low pressure of 3.0 ..
3.5 bar at the compressor inlet until the full opening of the valve.
In case of warm chambers, the pressure may be higher. In this case,
only the freezer may be switched on and then add the cooler.
open, it sensing the pressure of the liquid for
OM-RCWC-04D11
so that the
2014
11