Parameter Setting
• Some parameters are activated/deactivated depending on the model or setting of
other parameters.
• The 'Parameter mask' feature, which hide unnecessary or inactive parameters, and
the 'User parameter group' feature, which quickly and easily set up certain parameters
that are frequently used, can be set up in DAQMaster.
• Refer to the user manual for the details.
■ Parameter 1 group
Parameter
Display Default
Control output
RUN/STOP
R-S
Multi SV selection
SV-N
SV-0
Heater current
monitoring
CT-A
Alarm output1 low limit
AL!L
1550
Alarm output1 high limit
AL!H
1550
Alarm output2 low limit
AL@L
1550
Alarm output2 high limit
AL@H
1550
Alarm output3 low limit
AL#L
1550
Alarm output3 high limit
AL#H
1550
Multi SV 0
SV-0
0000
Multi SV 1
SV-1
0000
Multi SV 2
SV-2
0000
Multi SV 3
SV-3
0000
■ Parameter 2 group
Parameter
Display Default
Auto tuning RUN/STOP
AT
Heating proportional
band
H-P
01)0
Cooling proportional
band
C-P
01)0
Heating integral time
H-1
0000
Cooling integral time
C-1
0000
Heating derivative time
H-D
0000
Cooling derivative time
C-D
0000
Dead overlap band
DB
0000
Manual reset
REST
05)0
Heating hysteresis
hHYS
Heating OFF offset
hOST
Cooling hysteresis
cHYS
Cooling OFF offset
cOST
MV low limit
L-MV
`0)0
MV high limit
H-MV
10)0
RAMP up change rate
RAMU
RAMP down change rate
RAMD
RAMP time unit
rUNT
■ Parameter 3 group
Parameter
Display Default
Input specification
IN-T
KCaH
Temperature unit
UNIT
><?C
Analog low limit
L-RG
0)00
Analog high limit
H-RG
1)00
Scaling decimal point
DOT
Low limit scale
L-SC
00)0
High limit scale
H-SC
10)0
Display unit
dUNT
>?/O
Input correction
IN-B
0000
Input digital filter
MAvF
00)1
SV low limit
L-SV
-200
SV high limit
H-SV
1350
HEAT
(Normal
Control output mode
O-FT
(Heating&
(Normal
Control type
C-MD
(Heating&
Cooling-
Auto tuning mode
AtT
TUN1
OUT1 control output
selection
OUT1
CURR
OUT1 SSR drive output
type
O!SR
STND
OUT1 current output
range
O!MA
4-20
OUT2 control output
selection
OUT2
CURR
OUT2 current output
range
O@MA
4-20
Heating control cycle
02)0
(Relay)
H-T
Cooling control cycle
00@0
C-T
■ Parameter 4 group
Parameter
Display Default
Alarm output1 Operation
mode
RUN
AL-1
Alarm output1 Option
AL!T
Alarm output1 Hysteresis
A!HY
Alarm output1 contact
)0
type
Alarm output1 ON delay
time
A!ON
Alarm output1 OFF delay
time
A!OF
Alarm output2 Operation
mode
AL-2
Alarm output2 Option
AL@T
Alarm output2 Hysteresis
A@HY
Alarm output2 contact
type
Alarm output2 ON delay
time
A@ON
Alarm output2 OFF delay
time
OFF
A@OF
Alarm output3 Operation
mode
AL-3
Alarm output3 Option
AL#T
Alarm output3 Hysteresis
A#HY
Alarm output3 contact
type
Alarm output3 ON delay
time
A#ON
Alarm output3 OFF delay
time
A#OF
LBA time
002
LBaT
000
LBA band
002
LBaB
Analog Transmission
000
output1 Mode
AoM1
Transmission output1
low limit
FsL1
000
Transmission output1
000
high limit
FsH1
MIN
Analog Transmission
output2 Mode
AoM2
Transmission output2
low limit
FsL2
Transmission output2
high limit
FsH2
Communication address
ADRS
Communication speed
)0
Comm. parity bit
PRTY
Comm. stop bit
Response time
RSWT
Comm. write
COMW
■ Parameter 5 group
Parameter
Display Default
Multi SV number
MtSV
Digital input key
type)
DI-K
Digital input1 Terminal
Function
H-C
DI-1
Digital input2 Terminal
Cooling
Function
type)
DI-2
Manual control, initial MV
PID
ItMV
Manual control, preset
type)
MV
PrMV
Sensor error MV
pP
ErMV
Control stop MV
StMV
Control stop alarm
type)
output
StAL
User level
USER
SV setting lock
LcSV
Parameter 1 group lock
LcP1
Parameter 2 group lock
LcP2
Parameter 3 group lock
LcP3
Parameter 4 group lock
LcP4
Parameter 5 group lock
LcPS
Password setting
(SSR)
Function: Alarm
88* 8
Alarm
Alarm
operation
option
■ Operation
Name
Alarm operation
-
-
Deviation
high limit
DVCC
High deviation: Set as 10℃ High deviation: Set as -10℃
AL-A
001
Deviation
A!N
NO
low limit
Low deviation: Set as 10℃
0000
0000
Deviation
high, low
]]DV
limit
AL-A
001
Deviation
A@N
NO
high, low
limit reverse
0000
OFF
Absolute
0000
value high
limit
OFF
Absolute value: Set as 90℃ Absolute value: Set as 110℃
AL-A
001
Absolute
value low
A#N
NO
limit
Absolute value: Set as 90℃ Absolute value: Set as 110℃
0000
Sensor break -
0000
Heater break -
0000
002
(003)
Loop break
-
PV
■ Option
-200
Name
Description
1350
Standard
If it is an alarm condition, alarm output is ON. If it is a clear alarm
alarm
condition, alarm output is OFF.
PV
If it is an alarm condition, alarm output is ON and maintains ON
Alarm latch
status.
-200
First alarm condition is ignored and from second alarm
Standby
condition, standard alarm operates. When power is supplied
1350
sequence 1
and it is an alarm condition, this first alarm condition is ignored
01
and from the second alarm condition, standard alarm operates.
BPS
96
Alarm
If it is an alarm condition, it operates both alarm latch and
NONE
latch and
standby sequence. When power is supplied and it is an alarm
STP
2
standby
condition, this first alarm condition is ignored and from the
sequence 1
second 1alarm condition, alarm latch operates.
20
EnA
First alarm condition is ignored and from second alarm
condition, standard alarm operates. When re-applied standby
Standby
sequence and if it is alarm condition, alarm output does
sequence 2
not turn ON. After clearing alarm condition, standard alarm
operates.
1
Basic operation is same as alarm latch and standby sequence1.
STOP
Alarm
It operates not only by power ON/OFF, but also alarm set value,
latch and
OFF
or alarm option changing. When re-applied standby sequence
standby
and if it is alarm condition, alarm output does not turn ON.
sequence 2
OFF
After clearing alarm condition, alarm latch operates.
AUTO
00)0
00)0
00)0
CONT
STND
OFF
OFF
OFF
OFF
OFF
OFF
PWD
0000
Set both alarm operation and alarm option by combining.
Each alarm operates individually in two alarm output models.
When the current temperature is out of alarm range, alarm clears
automatically.
OFF
H
ON
OFF
H
ON
SV
PV
PV
SV
100℃
110℃
90℃
100℃
ON
H
OFF
ON
H
PV
SV
SV
PV
90℃
100℃
100℃
110℃
Low deviation: Set as -10℃
ON
H
OFF
H
ON
PV
SV
PV
90℃
100℃
110℃
High, Low deviation: Set as 10℃
OFF
H
ON
H
OFF
PV
SV
PV
90℃
100℃
110℃
High, Low deviation: Set as 10℃
H
ON
OFF
H
ON
PV
SV
SV
PV
90℃
100℃
100℃
110℃
ON
H
OFF
ON
H
PV
SV
SV
PV
100℃
110℃
90℃
100℃
• H: Alarm output hysteresis
Description
No alarm output
If deviation between PV and
SV as high-limit is higher
than set value of deviation
temperature, the alarm
output will be ON.
If deviation between PV
OFF
and SV as low limit is higher
than set value of deviation
temperature, the alarm
output will be ON.
If deviation between PV
and SV as high/low-limit
is higher than set value of
deviation temperature, the
alarm output will be ON.
If deviation between PV and
SV as high/low-limit is lower
than set value of deviation
temperature, the alarm
output will be OFF.
If PV is higher than the
absolute value, the output
will be ON.
OFF
If PV is lower than the
absolute value, the output
will be ON.
It will be ON when it detects
sensor disconnection.
It will be ON when it detects
heater disconnection.
It will be ON when it detects
loop disconnection.
Condition
of re-apply
-
-
Power ON
Power ON,
change SV,
change
alarm
temperature
/ operation
or change
STOP to RUN
mode